Advertisement

Fire Technology

, Volume 53, Issue 1, pp 211–226 | Cite as

Characterization of Stack Effect in High-Rise Buildings Under Winter Conditions, Including the Impact of Stairwell Pressurization

Article

Abstract

To characterize the magnitude of stack effect within stairwells and elevator shafts, differential pressure measurements were taken in fifteen (15) high-rise buildings in four (4) different cities (Cleveland, Baltimore, Minneapolis, and Philadelphia) during the winter months of January–March, 2013. Test buildings ranged in height from 44 m to 150 m (143 ft–492 ft). Outside temperatures during testing ranged from −12°C to 15°C (10°F–59°F). Based on the differential pressures measured, there was evidence of winter stack effect in all buildings tested. On the lower levels of all buildings, air was observed flowing from the building into the stairwells and elevator hoistways with pressure differential magnitudes ranging from −2.7 Pa to −24.9 Pa, −12.0 Pa average (−0.011 in. w.g. to −0.100 in. w.g., −0.048 in. w.g. average). Similarly, in most buildings (excluding Buildings 6 and 7) air was observed flowing from the stair and elevator hoistways into the building on the upper levels with pressure differential magnitudes ranging from 0.5 Pa to 34.9 Pa, 11.2 Pa average (0.002 in. w.g. to 0.140 in. w.g., 0.045 in. w.g. average). Under winter conditions, the data suggests that large quantities of air can migrate, floor-to-floor, via unprotected elevator shafts. Data further suggests activation of the stairwell pressurization system can increase vertical air movement via unprotected elevator shafts. This behavior is expected to impact the movement of smoke floor-to-floor during a fire, as airflow is indicative of smoke migration. The exterior stack force on the building’s envelope (governed by the building’s height and temperature differential between the building interior and exterior) does not always translate proportionally to shaft-to-building differential pressures (i.e., “stack effect”), as each building is unique. Although a building’s height and outside temperature play important roles in determining vertical airflow movement within a building, height alone was not found to be a good predictor of vertical airflow (or smoke movement) within the building due to stack effect. Other variables, such as architectural layout, architectural leakage, wind effects, and ventilation systems should all be considered. Simplified algebraic calculations (i.e. hand calculations) do not treat the building as a complete system, and do not account for all variables involved. Therefore, simplified algebraic calculations may result in inaccurate shaft-to-building differential pressure predictions. Based on this analysis, unless conservative leakage values are used, the simplified algebraic calculations may underpredict the shaft-to-building differential pressures. Using simplified algebraic calculations may be suitable for preliminary approximations, however, for design purposes a more complex analysis is recommended. The more complex analysis should consider other variables that affect pressure differentials such as changes in architectural layout and envelope leakage from floor-to-floor, HVAC systems, and wind.

Keywords

Stack effect Smoke control Stairwell pressurization Elevator pressurization Elevator lobby Building envelope Airtightness Infiltration Leakage 

References

  1. 1.
    NFPA 92 (2012) Standard for smoke control systems, National Fire Protection Association, QuincyGoogle Scholar
  2. 2.
    Klote JH, Milke JA, Turnbull PG, Kashef A, Ferreira MJ (2012) Handbook of smoke control engineering. American Society for Heating Refrigeration and Air Conditioning Engineers, AtlantaGoogle Scholar
  3. 3.
    NFPA 80 (2013) Standard for fire doors and other opening protectives, National Fire Protection Association, QuincyGoogle Scholar
  4. 4.
    Mowrer, F.W, Milke, J.A., Torero, J.L., (2004) A Comparison of Driving Force for Smoke Movement in Building,” Journal of Fire Protection Engineering, Vol. 14, No. 4, Sage Publications, London, UKGoogle Scholar
  5. 5.
    Walton GN, Dols S (2005) CONTAM 2.4 user guide and program documentation. NISIR 7251, National Institute of Standards and Technology, GaithersburgGoogle Scholar
  6. 6.
    NFPA 92A (2006) Standard for smoke-control systems utilizing barriers and pressure differences, National Fire Protection Association, QuincyGoogle Scholar
  7. 7.
    Miller RS, Beasley D (2009) On stairwell and elevator shaft pressurization for smoke control in tall buildings. Build Environ 44: 1306–1317CrossRefGoogle Scholar
  8. 8.
    Bowers DC, Ellison JR, Beasley DE, Miller RS (2010) Numerical study of elevator and stairwell pressurization systems using detailed building models. In: 8th international conference on performance-based codes and fire safety design methods, Society of Fire Protection Engineers, Lund, 16–18 June 2010Google Scholar
  9. 9.
    Persily AK (1998) Airtightness of commercial and institutional buildings: blowing holes in the myth of tight buildings. In: Proceeding of thermal performance of the exterior envelopes of buildings VIIGoogle Scholar
  10. 10.
    Emmerich SJ, Persily AK (2005) Airtightness of Commercial Buildings in the U.S, AIVC ConferenceGoogle Scholar
  11. 11.
    Emmerich SJ, Persily AK (2011) U.S. Commercial Building Airtightness Requirements and Measurements, National Institute of Standards and Technology, AIVC Conference, BrusselsGoogle Scholar
  12. 12.
    Sherman MH, Matson NE (2002) Airtightness of New U.S. Homes: a preliminary report, LBNL-48671, Lawrence Berkeley National LaboratoryGoogle Scholar
  13. 13.
    ICC (2011) International energy conservation code, International Code Council, Inc.Google Scholar
  14. 14.
    USACE (2009) Building air tightness requirements, US Army Corps of Engineers Engineering and Construction, Bulletin No. 2009–29.Google Scholar
  15. 15.
    Zhivov A (2011) New requirements to the United States Army Buildings air tightness, AIVC Workshop, BrusselsGoogle Scholar

Copyright information

© Springer Science+Business Media New York 2016

Authors and Affiliations

  1. 1.Jensen HughesBaltimoreUSA

Personalised recommendations