Abstract
Nuisance alarms have been identified as a leading cause of disabled smoke alarms in homes. In the 2013 Edition of NFPA 72, National Fire Alarm and Signaling Code, the Technical Committee approved requiring household alarms and detectors installed between 6 ft (1.8 m) and 20 ft (6.1 m) of cooking appliances to be listed for resistance to common cooking sources 2016 and for all household alarms, and detectors to be listed for resistance to common nuisances by 2019, respectively. There is currently no clear understanding of how “resistance to common nuisance sources” should be defined within these requirements. In this paper, Statistical data, surveys, and alarm installations were assessed to quantify the potential impacts of reducing nuisance alarms toward overall public safety and reduction of fire loss. Based on these reports, it has been estimated that elimination of nuisance alarms may reduce annual U.S. fire deaths by as much as 10%, or 214 deaths per year (1050 injuries). This number does not account for negative potential consequences on death and injury rates, such as increased alarm costs or decreased sensitivity to real fires. A review of laboratory test data and studies evaluating household installation performance was conducted to identify and characterize common household nuisance sources, such as cooking (60% to 80% of nuisance alarms), water mist (1% to 40%), or increased sensitivity from long term contamination (up to 70% of nuisance alarms). Detailed recommendations are made based on existing data to address remaining information gaps and develop new performance test protocols in ANSI/UL 217 and ANSI/UL 268 product standards in order to meet the NFPA 72-2013 requirements.
Similar content being viewed by others
References
Smith CL (1994) Smoke detector operability survey report on findings. U.S. Consumer Product Safety Commission, Washington, DC
Ahrens M (2011) Smoke alarms in U.S. home fires, NFPA 2011 National Fire Protection Association, Quincy
Gottuk DT (2010) Single-and multiple-station alarms and household fire alarm systems, Chapter 29, NFPA 72—National fire alarm and signaling code handbook, 6th edn, National Fire Protection Association, Quincy, pp. 669–718
Smith L (1995) Fire incident study: national smoke detector project. Consumer Product Safety Commission, Bethesda
Shapiro J (1994) Smoke detector operability survey, engineering laboratory analysis, Appendix B. Engineering Analysis Report, revised, Shapiro J. US Consumer Product Safety Commission, Directorate for Engineering Sciences, Division of Engineering Laboratory, Bethesda October 1994
Mickalide A, Validzic A (1999) Smoke alarm maintenance in low income families. Am J Public Health 89(10):1584
Kuklinski D, Berger L, Weaver J (1996) Smoke detector nuisance alarms: a field study in a native American Community. NFPA J, 90(5), National Fire Protection Association, Quincy, MA pp. 65–72
Rowland D et al (2002) prevalence of working smoke alarms in local authority inner city housing: randomized controlled trial. BMJ. 325:998–1001
Fazzini, Perkins R, Grossman D (2000) Ionization and photoelectric smoke alarms in Rural Alaskan Homes, West J Med, 173(2):89–92
Mueller B et al. (2008) Randomized controlled trial of ionization and photoelectric smoke alarm functionality. Inj Prev 14:80–86
Campbell Delong Resources, Inc. (2003) Barriers to maintaining working smoke alarms, service area demographic study and interview research, conducted for Tualatin Valley Fire and Rescue, Portland, May 2003
Wilson J et al. (2008) Evaluation of the “10-Year” Smoke Alarm Project, National Center for Healthy Housing, Prepared for the Center for Disease Control and Prevention, October 2008
Lee A, Pineda D (2010) Smoke alarms—pilot study of nuisance alarms associated with cooking. CPSC, Bethesda, March 2010
Ahrens M (2011), Unwanted fire alarms, NFPA 2011, National Fire Protection Association, Quincy, April 2011
Yang J, Jones MP, Cheng G, Ramirez M, Taylor C, Peek-Asa C (2011) Do nuisance alarms decrease functionality of smoke alarms near the kitchen? Findings from a randomized control trial. J Inj Prev 17(3):160–165
Cleary T, Chernovsky A (2013) Smoke alarm performance in kitchen fires and nuisance alarm scenarios. NIST TN-1784 Report, January 2013
ADL (Arthur D. Little, Inc.) (2001) Technical, practical and manufacturing feasibility of technologies to address surface cooking fires, May 2001
Primaira LLC (2011) Pan temperature-limiting control technology to reduce incidence of unattended cooking fires, prepared for United States Consumer Product Safety Commission
Wang A, Wang J, Yang Z, Zu M (2004) Research on Dust-proof Performance of Photoelectric Smoke Detector. In: 2004 AUBE Conference Proceedings, Duisburg, Germany, September 14–16 2004
Cambridge Times (2007) Put a Flea Collar on your Smoke Alarm, web editorial, 13 June 2007
Mulholland G, Liu BYU (1980) Response of smoke detectors to monodisperse aerosols. NBS J Res 85:223–238
Fabian T, Gandhi P (2007) Smoke Characterization Project. Underwriters Laboratories, Northbrook
Bukowski RW, Mulholland GW (1978) Smoke detector design and smoke properties, Center for Fire Research, National Engineering Laboratories, National Bureau of Standards, Washington DC, November 1978
Mulholland GW (2008) Smoke production and properties, Section 2, Chapter 13, SFPE handbook of fire protection engineering, 4th edn, Society of Fire Protection Engineers
Newman JS, Steciak J (1987) Characterization of particulates from diffusion flames. Combust Flame 67:55–64
Kuhlbusch T et al (2009) Measurement of elemental and organic carbon in Europe, JRC Scientifc and Technical Reports, EUR 23992 EN-2009, Ispra
Widmann J et al. (2004) Measurement of the optical extinction coefficient of combustion-generated aerosol. National Institute of Standards and Technology, Gaithersburg
Cleary T, Donnelly M, Grosshandler W, The fire emulator/detector evaluator: design, operation, and performance. In: 1999 AUBE Conference Proceedings, Duisburg, Germany, 16–18 March 1999
Cleary TG, Grosshandler W, Chernovsky A (1999) Smoke detector response to nuisance aerosols. In: 1999 AUBE Conference Proceedings, Duisburg, 16–18 March 1999
Bukowski R et al (2004) Performance of home smoke alarms analysis of the response of several available technologies in residential fire settings, NIST Technical Note 1455-1 (Revision), National Institute of Standards and Technology, Gaithersburg
Cleary T (2003) Home Smoke Alarm Project, Alarm Responses to Nuisance Sources, Report of FR 1419, National Institute of Standards and Technology, Gaithersburg
Cleary T (2004) Time resolved size distributions of test smokes and nuisance aerosol. In: 2004 AUBE Conference Proceedings, Duisburg, 14–16 Sept 2004
Cleary T, Yang J (2009) Prediction of light scattering and ionization chamber sensor response to smolder smoke aerosols. In: 2009 AUBE Conference Proceedings, Duisburg, 8–10 Sept 2009
Cleary T (2004) A test methodology for multiple sensor—multiple criteria alarms. In: 2004 AUBE Conference Proceedings, Duisburg, 14–16 Sept 2004
Cleary T Characterization of Residential Nuisance Sources, NIST Technical Note in preparation
Cleary T (2013) Characterization of residential nuisance sources. In: Presentation at UL 217 Task Group on Nuisance Alarms, 21 Nov 2013
Qiyuan X, Hongyong Y, Yongming Z (2002–2003) Experimental study on the sensitivity and nuisance immunity of smoke detector. J Appl Fire Sci 11(4):323–334
Feng J, Milke J (2013) Analysis of the response of smoke detectors to smoldering fires and nuisance sources. University of Maryland study, Prepared for Maryland Industrial Partnerships and USI Electric, p 29
Chen N (2004) A smoke particle measuring method of laser scattering and it’s applied researches. In: 2004 AUBE Conference Proceedings, Duisburg, Germany, 14–16 Sept 2004
Fabian T, Zevotek R, Milke J. Smoke alarm response in one and two-story residential structures. In: Suppression, Detection and Signaling Research and Application Symposium (SUPDET), Orlando, February 25th–March 1st 2013, pp 27
Dinaburg J, Gottuk DT (2011) Home Cooking Fire Mitigation: Technology Assessment—Final Report. Prepared for The Fire Protection Research Foundation, Quincy, MA, HAI Project #1DTG0 2049.006, 31 October 2011
Dinaburg J, Gottuk DT (2013) Development of standardized testing for range cooking fire mitigation technologies. In: Presentation at UL 217 Task Group on Nuisance Alarms, 21 Nov 2013
Huboyo H et al (2011) Indoor PM2.5 Characteristics and CO Concentration Related to Water-Based and Oil-Based Cooking Emissions Using a Gas Stove. In: Aerosol and Air Quality Research, 11, Taiwan Association for Aerosol Research, Tokyo, Japan, 2011, pp. 401–411
Edwards et al (2006) An inexpensive dual-chamber particle monitor. J Air Waste Manag Assoc 56:789–799
Litton C, Smith K, Edwards R, Allen T (2004) Combined optical and ionization techniques for measurement and characterization of sub-micrometer aerosols. In: 2004 AUBE Conference Proceedings, Duisburg, Germany, 14–16 Sept 2004
Wallace L et al (2011) Ultrafine particles: 3 years of measurements in the NIST test house. National Institute of Standards and Technology. Gaithersburg
See SW, Balasubramanian R (2008) Chemical characteristics of fine particles emitted from different gas cooking methods. Atmos Environ 42:8852–8862
Buonanno G, Stabile L, Morawska L (2009) Particle emission factors during cooking activities. Atmos Environ, 43(20):3235–3242
To W et al (2007) Emission of carcinogenic components from commercial kitchens in Hong Kong. SAGE Publications. doi:10.1177/1420326X06074500. Accessible online at http://ibe.sagepub.com
Weast RC (1988) CRC handbook of chemistry and physics, 1st Student edn. CRC Press, Inc., Boca Raton
Fang YD, Liu JH, Lin L, Liao GX (2006) Fullscale experimental studies on extinguishing cooking oil fires with water mist. Combust Sci Technol 12:318–322
Tian L, Zhang G, Zhang Q, Moschandreas DJ, Hao J, Lin J, Liu Y The impact of kitchen activities on indoor pollutant concentrations. Indoor Built Environ 17:377–383
Tsongas G (1995) Carbon monoxide from ovens: a serious IAQ problem. Home Energy Magazine Online, September/October 1995
Representative for Kidde, Telephone Interview, 4 Feb 2014
Wolin SD, Ryder NL, Leprince F, Milke JA, Mowrer FW, Torero JL Measurements of smoke characteristics in HVAC ducts. Fire Technol 37(4):363–395. doi:10.1023/A:1012776916407
Acknowledgments
The compilation and review of the data in this paper was conducted at the request and with support from National Fire Protection Research Foundation.
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Dinaburg, J., Gottuk, D. Smoke Alarm Nuisance Source Characterization: Review and Recommendations. Fire Technol 52, 1197–1233 (2016). https://doi.org/10.1007/s10694-015-0502-1
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s10694-015-0502-1