Aging condition assessment of transformer oil-immersed cellulosic insulation based upon the average activation energy method

  • Original Research
  • Published:
Cellulose Aims and scope Submit manuscript

Abstract

It is widely accepted that the service life of transformer oil–paper insulation is determined by the aging condition of transformer cellulosic insulation. Therefore, it is rather meaningful to accurately and reliably evaluate the aging condition of transformer cellulose insulation. Existing studies have shown that activation energy can eliminate the temperature effect on the frequency dielectric spectroscopy, however, the traditional activation energy might not be suitable for assessing the aging condition of transformer cellulosic insulation. The aim of the work is to assess the aging condition of cellulosic insulation by using average activation energy technique. The experiment process is firstly discussed. Then, the second-order dynamic equation formed by Arrhenius equation and Ekenstam equation is strictly investigated to accurately calculate the degree of polymerization value of transformer cellulosic insulation. The experimental results preliminarily show that the average activation energy can effectively assess aging condition of transformer cellulosic insulation.

Graphical abstract

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11

Similar content being viewed by others

References

  • Abu-Siada A, Lai S, Islam S (2012) A novel fuzzy-logic approach for furan estimation in transformer oil. IEEE Trans Power Deliv 27:469–474

    Article  CAS  Google Scholar 

  • Arroyo OH, Fofana I, Jalbert J, Ryadi M (2015) Relationships between methanol marker and mechanical performance of electrical insulation papers for power transformers under accelerated thermal aging. IEEE Trans Dielectr Electr Insul 22(6):3625–3632

    Article  Google Scholar 

  • Arroyo OH, Jalbert J, Fofana I, Ryadi M (2017) Temperature dependence of methanol and the tensile strength of insulation paper: kinetics of the changes of mechanical properties during ageing. Cellul J Article 24(2):1031–1039

    Article  CAS  Google Scholar 

  • Calvini P (2005) The influence of levelling-off degree of polymerization on the kinetics of cellulose degradation. Cellulose 12:445–447. https://doi.org/10.1007/s10570-005-2206-z

    Article  CAS  Google Scholar 

  • Calvini P, Gorassini A, Merlani Antonio L (2008) On the kinetics of cellulose degradation: looking beyond the pseudo zero order rate equation. Cellulose 15(2):193–203. https://doi.org/10.1007/s10570-007-9162-8

    Article  CAS  Google Scholar 

  • Ekenstam A (1936) The behavior of cellulose in mineral acid solutions: kinetic study of the decomposition of cellulose in acid solutions. BER 69:540–553

    Google Scholar 

  • Emsley AM, Heywood RJ (1997) On the kinetics of degradation of cellulose. Cellulose 4:1–5

    Article  CAS  Google Scholar 

  • Emsley AM, Stevens GC (1994) Kinetics and mechanisms of the low-temperature degradation of cellulose. Cellulose 1:26–56

    Article  CAS  Google Scholar 

  • Emsley AM, Xiao X, Heywood R (2000) Degradation of cellulosic insulation in power transformers. Part 2: formation of furan products in insulating oil. IEE Proc Sci Meas Technol 147:110–114

    Article  CAS  Google Scholar 

  • Fofana I, Hemmatjou H, Meghnefi F (2011) Effect of thermal transient on the polarization and depolarization current measurements of oil–paper insulation. IEEE Trans Dielectr Electr Insul 18:513–520

    Article  CAS  Google Scholar 

  • Gao J, Yang LJ, Wang YY (2016) Effect of moisture and thermal degradation on the activation energy of oil–paper insulation in frequency domain spectroscope measurement. IET Gener Transm Distrib 10:2042–2049

    Article  Google Scholar 

  • Jalbert J, Gilbert R, Denos Y, Gervais P (2012) Methanol: a novel approach to power transformer asset management. IEEE Trans Power Deliv 27(2):514–520

    Article  CAS  Google Scholar 

  • Jalbert J, Celis ER, Duchesne S, Morin B et al (2015) Kinetics of the production of chain-end groups and methanol from the depolymerization of cellulose during the ageing of paper/oil systems. Part 3: extension of the study under temperature conditions over 120 °C. Cellul J Article 22(1):829–848

    Article  CAS  Google Scholar 

  • Jinscher AK (1996) Dielectric relaxation in solids. J Phys D Appl Phys 32(14):57–70

    Article  Google Scholar 

  • Koch M, Prevost T (2012) Analysis of dielectric response measurements for condition assessment of oil–paper transformer insulation. IEEE Trans Dielectr Electr Insul 19:1908–1915

    Article  Google Scholar 

  • Koufakis E, Halevidis C, Polykrati A (2012) Calculation of the activation energy of oil–paper insulation in a distribution transformer. IEEE Electr Insul Mag 28:52–58

    Article  Google Scholar 

  • Lelekakis N, Martin D, Wijaya J (2012a) Ageing rate of paper insulation used in power transformers. Part 1: oil/paper system with low oxygen concentration. IEEE Trans Dielectr Electr Insul 19:1999–2008

    Article  CAS  Google Scholar 

  • Lelekakis N, Martin D, Wijaya J (2012b) Ageing rate of paper insulation used in power transformers. Part 2: oil/paper system with medium and high oxygen concentration. IEEE Trans Dielectr Electr Insul 19:2009–2018

    Article  CAS  Google Scholar 

  • Liao RJ, Sun HG, Gong J et al (2011) Ageing kinetic model and life time model of oil–paper insulation in transformers. High Volt Eng 37:1576–1583 (in Chinese)

    CAS  Google Scholar 

  • Liao RJ, Hao J, Chen G, Yang LJ (2012) Quantitative analysis of ageing condition of oil–paper insulation by frequency domain spectroscopy. IEEE Trans Dielectr Electr Insul 19:821–830

    Article  CAS  Google Scholar 

  • Liao RJ, Liu JF, Yang LJ et al (2015a) Quantitative analysis of insulation condition of oil–paper insulation based on frequency domain spectroscopy. IEEE Trans Dielecctr Electr Insul 22:322–334

    Article  CAS  Google Scholar 

  • Liao RJ, Liu JF, Yang LJ, Gao J, Zhang YY, Lv Y, Zheng H (2015b) Understanding and analysis on frequency dielectric parameter for quantitative diagnosis of moisture content in paper–oil insulation system. IET Electr Power Appl 9:213–222

    Article  Google Scholar 

  • Liao RJ, Liu JF, Yang LJ et al (2015c) Extraction of frequency domain dielectric characteristic parameter of oil–paper insulation for transformer condition assessment. Electr Power Compon Syst 43:578–587

    Article  Google Scholar 

  • Linhjell D, Lundgaard LE, Gafvert U (2007) Dielectric response of mineral oil impregnated cellulose and the impact of aging. IEEE Trans Dielectr Electr Insul 14:156–169

    Article  CAS  Google Scholar 

  • Liu JF, Liao RJ, Zhang Y, Gong C, Wang C, Gao J (2015) Condition evaluation for aging state of transformer oil–paper insulation based on time-frequency domain dielectric characteristics. Electr Power Compon Syst 43:759–769

    Article  Google Scholar 

  • Liu JF, Zheng HB, Zhang YY, Wei H, Liao RJ (2017) Grey relational analysis for insulation condition assessment of power transformers based upon conventional dielectric response measurement. Energies 10:1526

    Article  Google Scholar 

  • Liu JF, Zheng HB, Zhang YY (2018) Comparative investigation on the performance of modified system poles and traditional system poles obtained from PDC data for diagnosing the aging condition of transformer polymer insulation materials. Polymers 10:191

    Article  CAS  PubMed Central  Google Scholar 

  • Mukherjee M, Pradhan AK, Baral A, Chakravorti S (2017) A modified Maxwell model for modeling dielectric response of oil–paper insulation affected by radial and axial temperature gradients. IEEE Trans Dielectr Electr Insul 24:1000–1009

    Article  CAS  Google Scholar 

  • Prevost TA, Oommen TV (2006) Cellulose insulation in oil-filled power transformers: part I—history and development. IEEE Electr Insul Mag 22(1):28–35

    Article  Google Scholar 

  • Rodriguez-Celis EM, Duchesne S, Jalbert J, Ryadi M (2015) Understanding ethanol versus methanol formation from insulating paper in power transformers. Cellulose 22:3225–3236

    Article  CAS  Google Scholar 

  • Saha TK (2003) Review of modern diagnostic techniques for assessing insulation condition in aged transformers. IEEE Trans Dielectr Electr Insul 10:903–917

    Article  CAS  Google Scholar 

  • Saha TK, Purkait P (2008) Understanding the impacts of moisture and thermal aging on transformer’s insulation by dielectric response and molecular weight measurements. IEEE Trans Dielectr Electr Insul 15(2):568–582

    Article  Google Scholar 

  • Shi J, Wu CN, Wang XJ (2015) Life evaluation of insulation paper used in transformer by determining the activation energy. Mater Res Innov 19:164–167

    Article  CAS  Google Scholar 

  • Tang C, Zhang S, Wang X, Hao J (2018) Enhanced mechanical properties and thermal stability of cellulose insulation paper achieved by doping with melamine-grafted nano-SiO2. Cellulose 25(6):3619–3633

    Article  CAS  Google Scholar 

  • Thakur S, Sarathi R, Gautam R, Vinu R (2017) Thermal aging of cellulosic pressboard material and its surface discharge and chemical characterization. Cellulose 24:5197–5210

    Article  CAS  Google Scholar 

  • Verma HC, Baral A, Pradhan AK, Chakravorti SA (2017) A method to estimate activation energy of power transformer insulation using time domain spectroscopy data. IEEE Trans Power Deliv 24:3245–3253

    CAS  Google Scholar 

  • Wada J, Ueta G, Okabe S (2014) Method to evaluate the degradation condition of transformer insulating oil-experimental study on the hydrophilic and dissociative properties of degradation products. IEEE Trans Dielectr Electr Insul 21:873–881

    Article  CAS  Google Scholar 

  • Wang L, Tang C, Zhu S, Zhou S (2018) Terahertz time domain spectroscopy of transformer insulation paper after thermal aging intervals. Materials 11(11):2124

    Article  PubMed Central  Google Scholar 

  • Yang LJ, Peng P, Gao J, Liu X (2018) The range recognition of moisture and aging status of oil–paper insulation based on frequency domain dielectric response characteristic fingerprint. Trans China Electrotech Soc 33:2105–2114

    Google Scholar 

  • Zhang YY, Liu JF, Zheng HB, Wei H, Lian RJ (2017) Study on quantitative correlations between the ageing condition of transformer cellulose insulation and the large time constant obtained from the extended debye model. Energies 10:1842

    Article  Google Scholar 

  • Zhang YY, Liu JF, Zheng HB, Wang K (2018a) Feasibility of a universal approach for temperature correction in frequency domain spectroscopy of transformer insulation. IEEE Trans Dielectr Electr Insul 25:1766–1773

    Article  CAS  Google Scholar 

  • Zhang DN, Yun H, Zhan JY et al (2018b) Insulation condition diagnosis of oil-immersed paper insulation based on non-linear frequency-domain dielectric response. IEEE Trans Dielectr Electr Insul 25:1980–1988

    Article  CAS  Google Scholar 

  • Zheng HB, Zhang YY, Liu JF, Wei H, Zhao JH, Liao RJ (2018) A novel model based on wavelet LS-SVM integrated improved PSO algorithm for forecasting of dissolved gas contents in power transformers. Electr Power Syst Res 155:196–205

    Article  Google Scholar 

Download references

Acknowledgments

The authors acknowledge the National Natural Science Foundation of China (61473272; 51867003), the Natural Science Foundation of Guangxi (2018JJB160056; 2018JJB160064; 2018JJA160176). J.L., H.Z. and Y.Z. designed the algorithms and performed the writing, and they contributed equally to this work; H.Z. and Y.Z. are both corresponding authors; X.F., C.Z., B.L., J.W., G.R., and E.Z. analyzed the data; all authors have approved the submitted manuscript. The authors also thank the anonymous reviewers and the editor for their valuable comments.

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to H. Zheng.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Liu, J., Fan, X., Zheng, H. et al. Aging condition assessment of transformer oil-immersed cellulosic insulation based upon the average activation energy method. Cellulose 26, 3891–3908 (2019). https://doi.org/10.1007/s10570-019-02331-1

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s10570-019-02331-1

Keywords

Navigation