Advertisement

Seismic performance enhancement of high-voltage post insulators by a polyurethane spring isolation device

  • Tansu Gökçe
  • Ercan Yüksel
  • Engin Orakdöğen
Original Research

Abstract

High-voltage (HV) post insulators are vulnerable components of the electrical substations during strong earthquakes. It is rather hard to repair them in service. There are two controversial approaches to increase their seismic safety. They are application of the base stiffening techniques and utilization of the base isolation systems. A new low-cost seismic isolation device that is mounted underneath of HV post insulator is being proposed here to provide period elongation and supplementary damping. The seismic isolator consists of two steel plates, four polyurethane springs and a steel rod. Its cost is insignificant compared with price of HV post insulator. Quasi-static and shake table tests were performed on fixed base and isolated specimens. A set of historical acceleration records selected according to IEEE-693 were utilized in the dynamic tests. The supplementary damping provided by the isolation system was determined between 4 and 8%. The accelerations as well as base shear and base moment of HV post insulator were reduced about 20–70% thanks to the isolation system. The generated numerical models reproduced the experimental results. Consequently, the isolation system is capable to enhance the seismic safety of HV post insulators.

Keywords

Earthquake safety Seismic isolation Low-cost isolation Post insulator Polyurethane spring 

Notes

Acknowledgements

The first author was sponsored by Bideb 2211 Program of Scientific and Technological Research Council of Turkey (TUBITAK). The study was sponsored by the research funds of Istanbul Technical University (ITU BAP 39552). 550 kV HV post insulators were supplied by Güral Electric Company. The study was carried out in the Structural and Earthquake Engineering Laboratory (STEELab) of ITU. All supports are gratefully acknowledged.

References

  1. Akiyama H (1985) Earthquake-resistant limit-state design for buildings. University of Tokyo Press, TokyoGoogle Scholar
  2. Alessandri S, Giannini R, Paolacci F, Malena M (2015a) Seismic retrofitting of an HV circuit breaker using base isolation with wire rope. Part 1: preliminary test and analyses. Eng Struct 98:251–262CrossRefGoogle Scholar
  3. Alessandri S, Giannini R, Paolacci F, Malena M (2015b) Seismic retrofitting of an HV circuit breaker using base isolation with wire rope. Part 2: shaking table test validation. Eng Struct 98:263–274CrossRefGoogle Scholar
  4. Buckle I, Constantinou M, Dicleli M, Ghasemi H (2006) Seismic isolation of highway bridges (Report No. MCEER-06-SP07), MCEER, University at Buffalo, NYGoogle Scholar
  5. Chopra AK (2001) Dynamic of structures, theory and application to earthquake engineering, 4th edn. Prentice-Hall, Upper Saddle RiverGoogle Scholar
  6. Clemitson IR (2015) Castable polyurethane elastomers. CRC Press, Boca RatonCrossRefGoogle Scholar
  7. Davies P, Evrard G (2007) Accelerated ageing of polyurethanes for marine applications. Polym Degrad Stab 92(8):1455–1464CrossRefGoogle Scholar
  8. Falborski T, Jankowski R (2017) Experimental study on effectiveness of a prototype seismic isolation system made of polymeric bearings. Appl Sci 7(8):808CrossRefGoogle Scholar
  9. FEMA 461 (2007) Interim testing protocols for determining the seismic performance characteristics of structural and non-structural components. Applied Technology Council, CaliforniaGoogle Scholar
  10. FEMA P-695, (2009) Quantification of building seismic performance factors. Applied Technology Council for the Federal Emergency Management Agency, WashingtonGoogle Scholar
  11. Filiatrault A, Matt H (2006) Seismic response of high voltage electrical transformer-bushing systems. J Struct Eng 132–2:287–295CrossRefGoogle Scholar
  12. Gokce T, Yuksel E, Orakdogen E (2017) Seismic protection of high voltage bushings by using polyurethane springs. In: 16th world conference on earthquake engineering, Santiago, Chile, Paper no: 2381Google Scholar
  13. Gokce T, Orakdogen E, Yuksel E (2018) Failure mode investigation for high voltage porcelain insulators. In: 16th European conference on earthquake engineering, Thessaloniki, Greece, Paper no: 11334Google Scholar
  14. Hatami M, Ashtiany MG, Hosseini M (2004) Experimental and analytical study of a high voltage instrument transformer. In: 13th world conference on earthquake engineering, Vancouver, BC, Canada, Paper no: 2550Google Scholar
  15. IEEE 693 (1985 & 2006) Recommended practice for seismic design of substations. IEEE Standard Department, Piscataway, NJGoogle Scholar
  16. Jeong K, Choi E, Back SY, Kang JW (2016) Smart damper using sliding friction of aramid brake lining and self-centering of rubber springs. Int J Steel Struct 16(4):1239–1250CrossRefGoogle Scholar
  17. Koliou M, Filiatrault A, Reinhorn AM (2009) Seismic protection of electrical transformer bushing systems by stiffening techniques (Report No. MCEER-12-002), MCEER, University at Buffalo, NYGoogle Scholar
  18. Kong D, Reinhorn A (2009) Seismic evaluation and protection of high voltage disconnect switches. Lifeline earthquake engineering in a multihazard environment, ASCE, pp 221–231Google Scholar
  19. Lee D, Constantinou MC (2018) Combined horizontal–vertical seismic isolation system for high voltage–power transformers: development, testing and validation. Bull Earthq Eng 16:4273–4296CrossRefGoogle Scholar
  20. Lihong S, Zhiqiang L, Xue Y (2014) Experimental study of marine polyurethane isolator life. In: The 21st international congress on sound and vibration. Beijing, ChinaGoogle Scholar
  21. Mohammadpour S, Hosseini M (2017) Experimental system identification of a 63 kV substation post insulator and the development of its fragility curves by dynamic finite element analyses. Earthq Spectra 33(3):1149–1172CrossRefGoogle Scholar
  22. Murota N, Feng MQ, Liu GY (2006) Earthquake simulator testing of base-isolated power transformers. IEEE Trans Power Delivery 21–3:1291–1299CrossRefGoogle Scholar
  23. Oikonomou K, Constantinou MC, Reinhorn AM, Leon K Jr (2016) Seismic isolation of high voltage electrical power transformers (Report No. MCEER 16-0006), MCEER, University at Buffalo, NYGoogle Scholar
  24. Schiff A (1998) Guide to improved earthquake performance of electrical power systems (Report No. NIST GCR 98-757). National Institute for Standards and Testing, Washington, D.CGoogle Scholar
  25. SeismoStruct (2006) A computer program for static and dynamic nonlinear analysis of framed structures. Pavia, Italy. Seismosoft http://www.seismosoft.com
  26. Stearns C, Filiatrault A (2005) Electrical substation equipment interaction: experimental rigid conductor studies PEER Report 2004/09. Pacific Earthquake Engineering Research Center, College of Engineering University of California, BerkeleyGoogle Scholar
  27. Takhirov S, Fujisaki E, Kempner L, Riley M, Low B (2017) Full-scale component testing of seismic isolation devices and verification of their performance in full-scale system level tests on a shaking table. In: 7th international conference on advances in experimental structural engineering, Pavia, ItalyGoogle Scholar
  28. Villaverde R, Pardoen GC, Carnalla S (2001) Ground motion amplification at flange level of bushings mounted on electric substation transformers. Earthquake Eng Struct Dynam 30:621–632CrossRefGoogle Scholar
  29. Whittaker AS, Fenves GL, Gilani ASJ (2004) Earthquake performance of porcelain transformer bushings. Earthq Spectra 20:205–223CrossRefGoogle Scholar

Copyright information

© Springer Nature B.V. 2018

Authors and Affiliations

  1. 1.Institute for Science and TechnologyIstanbul Technical UniversityMaslak, IstanbulTurkey
  2. 2.Faculty of Civil EngineeringIstanbul Technical UniversityMaslak, IstanbulTurkey

Personalised recommendations