1 Introduction

Liquid jet impingement is used in industry when surfaces must be cooled or cleaned, since this process is characterized by high heat or mass transport rates in the vicinity of the impingement point. Liquid jet impingement heat transfer was extensively studied during the 1990’s experimentally and theoretically [1,2,3,4]. Liu et al. [2, 3] developed two different models describing the heat transfer depending on the liquid Prandtl number being above or below unity. The authors divide the wall flow driven by vertical impingement of a laminar jet onto a horizontal heated wall into several sections: For Pr > 1 these sections are the stagnation zone, the boundary layer development zone, lasting until the viscous boundary layer reaches the free surface, the similarity region, in which the temperature distribution across the film thickness is self-similar, followed by the transition to turbulence and eventually to the fully turbulent flow. The measurements of Stevens and Webb [5] indicated that the former division is also valid for a vertical set up. Highest heat transfer rates are found in the region of the stagnation zone and the region of thermal boundary layer development.

One of the important factors limiting the heat transfer rate during jet impingement is the splattering of liquid from the wall. Splattering has been typically observed for turbulent liquid jets and high nozzle-to-target distances (nozzle distances). Based on the velocity measurement of the splattered droplets, it has been assumed that the splattering takes place downstream the radial position (also known as the radius of splattering) rs = 5.71 dN [6], where dN denotes the nozzle diameter. Splattering is often quantified by the splattered mass fraction ξ, which is the ratio between the mass flow rates of the splattered liquid and impinging liquid [7,8,9,10,11,12]. Correlations describing the splattered mass fraction can be found in [9] for coherent jets (L/dN < 50) and pipe nozzles, as well as in [11] for disintegrated jets (L/dN ≥ 250). Both correlations state that ξ increases with the jet Weber number.

Several methods for heat transfer enhancement have been suggested, including artificial wall roughness [13], gas injection from capillary tubes, positioned at the jet centerline, into a liquid jet [14], and pulsation. Zumbrunnen and Aziz [15] investigated the influence of pulsation created by a cutter blade on heat transfer during impingement of water jets onto a horizontal wall. Using pulsation with frequencies up to 140 Hz lead to an enhancement of the heat transfer in the stagnation zone of up to 100% [15]. The enhancement, in this case, is related to a renewal of the thermal boundary layer, which was shown to become dominant for Strouhal number Sr ≥ 0.26 [15, 16]. The Strouhal number is defined by the pulsation frequency, the characteristic length and speed of the jet:

$$ \mathrm{Sr}=\mathrm{f}\ {\mathrm{d}}_{\mathrm{N}}/{\mathrm{u}}_{\mathrm{jet}} $$
(1)

Besides the pulses created by a cutter blade (rectangular pulse form), other pulse forms, such as sinusoidal, have been applied in an attempt to enhance the heat transport. However, they did not lead to similar enhancement factors or even to decreasing the heat transfer coefficient [17]. Further increase of the pulsation frequency results in a transformation of the intermittent jet into a droplet train and also does not lead to a further increase of the heat transfer rate [18, 19]. Ongoing research on pulsating impinging jets is focused on submerged gas jets. For instance, Middelberg and Herwig [20] investigated the heat transfer of pulsating air jets and find an enhancement in heat transfer of up to 60% in the stagnation flow area in comparison to the continuous jet. To the knowledge of the authors, the effect of pulsation on heat transfer by impingement of horizontal liquid jets on vertical walls has not been investigated yet.

The flow pattern resulting from the impact of a horizontal jet onto a vertical wall is schematically represented in Fig. 1. The impingement of a circular liquid jet onto a vertical wall is – as for the horizontal wall - accompanied by the formation of stagnation flow and the development of a thin liquid film, or the radial flow zone (RFZ, zone 1 in Fig. 1), in which the velocity is dominated by its radial component [21]. The radial flow zone is bounded by a hydraulic jump. However, in the case of a vertical wall, the latter is not circular as in the case of a normal impingement onto horizontal surfaces, but has an arc shape [11], as illustrated in Fig. 1. Since the velocity, and thus the heat and mass transfer rates, are reduced in the region of the hydraulic jump, the extent of the RFZ in the horizontal and vertical directions denoted by X and Y, respectively (see Fig. 1b), are of particular interest. Outside the hydraulic jump, a circumferential flow (or rope flow, 2) is formed, which merges with the RFZ considerably below the POI forming a falling film (3). For low nozzle distances, splattering is not significant, and the extent of RFZ in the horizontal direction can be predicted from the model equation suggested by Wilson [22]:

Fig. 1
figure 1

Schematic of the liquid flow pattern for continuous jet impingement in side view (a) and top view (b) with the radial flow zone (1), the rope flow (2), and the falling film zone (3)

$$ \mathrm{X}=0.276{\left(\frac{{\overset{.}{\mathrm{M}}}^3}{\upmu\ \upgamma\ \rho}\right)}^{\frac{1}{4}} $$
(2)

Equation (2) with the mass flow rate \( \overset{.}{M} \), the dynamic viscosity μ, the surface tension γ, and the liquid density ρ states that X only depends on the mass flow rate for the given liquid. Higher nozzle distances lead to more developed surface disturbances of the impinging jet, which generally causes splattering from the wall flow [8, 9, 11]. Since splattering leads to a reduction of the wall flow momentum, the extent of the RFZ in both directions is also reduced. In this case, the model developed in [11], in which the splattering is accounted for, provides a more accurate prediction of the RFZ extent.

The impingement of a pulsating jet (consisting of successive jet sections) leads to development of complex periodic wall flow patterns. The development of flow patterns between the impingements of two successive pulses (jet sections) typically can be subdivided into several phases: (i) the spreading phase directly after impingement, eventually leading into (ii) the quasi-steady phase, which lasts until the end of the jet section impingement phase. Phase (ii) exhibits the same flow pattern, as would result from continuous jet impingement and is characterized by a constant mass of water above the point of impingement (POI). After the jet is turned off (intermission of the impingement) phase (iii), the drainage of the wall film starts. It is expected that the drainage of the liquid stored in the rope above the impingement point contributes to convective heat transport and cooling of the heated wall without ongoing inflow of cooling liquid, and thus, could lead to improvement of resource efficiency of the jet impingement cooling process.

In the present work, the heat transfer between a horizontally impinging pulsating liquid jet and a vertical wall is investigated to discover if or to what extent jet pulsation leads to heat transfer enhancement. The range of jet impingement parameters and the range of pulsation parameters have been chosen in such a way that the duration of the spreading phase and the drainage phase are comparable with the duration of the impingement pulse. Experiments were performed at jet Reynolds numbers Re = 20700 − 59000 and pulsation frequencies f = 1 − 5 Hz with a pipe nozzle (dN = 4 mm), and nozzle-to-wall distances in the range from 3 to 167 nozzle diameters.

2 Experimental method

2.1 Experimental setup

The main part of the test setup used in this work is the open water circuit pictured in Fig. 2a, which has been also used in [11], where a detailed description can be found. During the measurement water is pumped from the tank (1) by a multistage centrifugal pump (2, IN-VB 2–140, Speck) passing through the Coriolis mass flow meter (TME 5, Heinrichs Messtechnik GmbH). The water temperature is kept at 20 ± 1 ° C using a counter flow heat exchanger and a bath thermostat (not depicted). The sectional valves (3, EV210B, Danfoss) are used to create the pulsation by either directing water to the tank or to the nozzle (4), where the liquid jet is formed. Both streams exhibit equal flow resistances. This leads to an intermittent pulsation form with an almost rectangular function of the nozzle pressure. The jet Reynolds number is then defined as follows:

$$ \operatorname{Re}=\frac{4\overset{.}{\mathrm{M}}}{\uppi\ {\mathrm{d}}_{\mathrm{N}}\ \upmu\ \mathrm{DC}} $$
(3)
Fig. 2
figure 2

a Schematic of the test stand used in this work: (1) tank, (2) centrifugal pump, (3) sectional valves, (4) nozzle, (5) wall with integrated heater, (6) & (7) collecting tubs, (8) sampling position, and (9) wet cell. b Drawing of heater and detailed cross section at a thermocouple position

In Eq. (3), DC is the duty cycle of the pulsation, which indicates the ratio of the mass flow rate through the nozzle to the total mass flow before the valves, \( \overset{.}{\mathrm{M}} \) the time-averaged mass flow rate through the nozzle, and μ the dynamic viscosity of water. On the one hand, with this definition of Re the liquid jets with different pulsation duty cycle, but with equal velocity at nozzle exit have equal Reynolds numbers. On the other hand, jets with equal average mass flow rates and equal nozzle diameters do not necessarily have the same Reynolds number. Anticipating that phase (ii) will be reached, jets with the same Reynolds number are able to wet approximately the same area.

In the wet cell (9), after passing the nozzle distance L, the jet impinges on the center of a plate, which is heated by the meandering wire heater (5, Fig. 2b). After impingement a part of liquid with the mass flow rate \( {\overset{.}{\mathrm{M}}}_{\mathrm{s}} \) is splattered, and the rest of the liquid with the mass flow rate\( {\overset{.}{\mathrm{M}}}_{\mathrm{r}} \) remains on the wall and cools the heater. Both mass flows are collected by separate tubs (6 & 7) and can be withdrawn from the circuit at the sampling point (8) into two separate containers. The nozzle is placed on a sled to be able to vary the distance L. In order to guarantee a horizontal impact, the nozzle’s orientation is slightly deviating from horizontal.

2.2 Heat transfer measurement

The heater plate is manufactured from nickel and has a cylindrical shape with a thickness of 8 mm and a radius of R = 67.5 mm according to Fig. 2b. It is glued into a polycarbonate frame on surface level. The meandering wire on the back side is connected to a 1.5 kW power supply (Delta Electronica 1500) and countered by a 2 mm thick aluminum plate to ensure a thermal contact. Additional thermal (Isoplan® 1000, 6 mm) and electric insulation is applied. Therefore, more than 97% of the introduced heat is conducted to the surface of the plate. Thermocouples were soldered in at surface level along the radial coordinate (r = 0, 4, 8, 16, 24, 32, 40, 48, 56, 63 mm) from the POI and allow the measurement of the wall temperature Tw(r) with a sampling rate of 60 Hz. The heater surface was countered with an aluminum sheet and heated to 300 °C. Solder was filled into holes before the thermocouples were inserted and fixed. After cooling the aluminum was removed and the heater surface was carefully sanded. The heater can be rotated around its axis to allow measurements along different directions from the POI. The water temperature at the nozzle inlet Tl is measured as well. Each experiment was carried out for 30 s after reaching a stationary state, which was indicated when the electric resistance of the meandering wire became stationary. The measurement data was gathered using LabVIEW® and then processed in Matlab®. The data was cut to fit a whole number of periods, e.g. 30 for f = 1 Hz. For each parametric setting 2–3 experiments were carried out on different days. Presented time-averaged temperatures in section 3 are averages of the different mean temperatures resulting from these experiments, while the error bars display maximum deviation from this mean. The wall temperatures can be used to characterize the heat transfer.

For equal Reynolds numbers defined in Eq. (3), the mass flow rate and thereby the heat transfer rate, can differ significantly. In order to quantify the heat transfer efficiency at a radial distance r from POI, we introduce a modified local Stanton number [Eq. (4)]. This parameter can be interpreted as a relation between the heat transferred from the wall to the fluid within a circular region with the center at the POI and the radius r, \( {\overset{.}{\mathrm{Q}}}_{1\mathrm{D}}\left(\mathrm{r}\right)=\overset{.}{\mathrm{Q}}\cdotp {\left(\mathrm{r}/\mathrm{R}\right)}^2 \), to the maximum heat \( {\overset{.}{\mathrm{Q}}}_{\mathrm{max}} \) that could be transferred, if the water temperature at the position r was uniform and equal to the wall temperature:

$$ \mathrm{St}=\frac{{\mathrm{A}}_{\mathrm{H}}\left(\mathrm{r}\right)\cdotp \mathrm{h}\cdotp \left({\mathrm{T}}_{\mathrm{w}}\left(\mathrm{r}\right)-{\mathrm{T}}_{\mathrm{l}}\right)}{\overset{.}{\mathrm{M}}\cdotp \mathrm{c}\cdotp \left({\mathrm{T}}_{\mathrm{w}}\left(\mathrm{r}\right)-{\mathrm{T}}_{\mathrm{l}}\right)}=\frac{\overset{.}{\mathrm{Q}}\cdotp {\left(\mathrm{r}/\mathrm{R}\right)}^2}{\overset{.}{\mathrm{M}}\cdotp \mathrm{c}\cdotp \left({\mathrm{T}}_{\mathrm{w}}\left(\mathrm{r}\right)-{\mathrm{T}}_{\mathrm{l}}\right)}=\frac{{\overset{.}{\mathrm{Q}}}_{1\mathrm{D}}\left(\mathrm{r}\right)}{{\overset{.}{\mathrm{Q}}}_{\mathrm{max}}\left(\mathrm{r}\right)} $$
(4)

In Eq. (4) h denotes the heat transfer coefficient, AH a circular part of the heater surface, and c the specific heat capacity. The heat flow\( {\overset{.}{\mathrm{Q}}}_{1\mathrm{D}}\left(\mathrm{r}\right)=\overset{.}{\mathrm{Q}}\cdotp {\left(\mathrm{r}/\mathrm{R}\right)}^2 \) is evaluated under an assumption that radial heat conduction within the heater plate is negligible. The mean modified Stanton number \( \overline{\mathrm{St}} \) is evaluated by averaging the Stanton numbers \( {\overline{\mathrm{St}}}_{\upvarphi} \) determined from temperature measurements at different radial positions as shown in Fig. 2b along the directions above, sideways (twice), and below the POI:

$$ {\overline{\mathrm{St}}}_{\upvarphi}=\frac{\overset{.}{\mathrm{Q}}}{\left({\overline{\mathrm{T}}}_{\mathrm{w}}-{\mathrm{T}}_{\mathrm{l}}\right)\cdotp \overset{.}{\mathrm{M}}\cdotp \mathrm{c}} $$
(5)
$$ {\overline{\mathrm{T}}}_{\mathrm{w}}=\frac{2\int_0^{\mathrm{R}}\mathrm{r}\ {\mathrm{T}}_{\mathrm{w}}\mathrm{dr}}{{\mathrm{R}}^2} $$
(6)

The spatial mean wall temperature \( {\overline{\mathrm{T}}}_{\mathrm{w}} \) in Eq. (5) is calculated using Eq. (6), with the temporal mean temperatures and a cubic spline interpolation with zero slope at r = 0 and r = R. The error bars shown in Figs. 8, 9 and 11b are based on the uncertainty of the Stanton number, taking into account uncertainties of mass flow rate (0.2%), temperatures (±0.2 K) and heat flow (3,3%) using error propagation.

2.3 Flow visualisation

In order to provide additional information about the wall-flow patterns governing the heat transport, high speed imaging was used. In a separate experiment the heater was exchanged by a transparent wall made of Plexiglas. The high speed camera (MotionBlitz EoSens Cube 7, Mikrotron GmbH) was mounted behind the transparent wall and was enlightened from the side of the nozzle. The images were taken with a frame rate fr = 1kHz and a shutter time ts = 10μs. The distance in pixels have been converted to millimeters using a reference image for the set camera position, giving 0.289 mm/Pi. Due to differences in the wetting properties of the materials, deviation between both experiments are possible. As the contact line, which is sensitive to wetting, is located outside the heated region on the polycarbonate, the deviations are negligible and the observed flow patterns are not affected.

3 Results and discussion

Before the heat transfer between wall and water is discussed, the developed flow patterns are described in detail along two examples. Figure 3a shows a set of images displaying the flow patterns at different time instants t after the jet section impingement for Re = 31000, nozzle distance L/dN = 3, pulsation frequency f = 1Hz and duty cycle of 50%. In order to revisit Fig. 3 in section 3.1, the heater size is marked by the bright area. It can be seen that during phase (i) the spreading wall flow reaches the border of the heater at t = 34 ms and reached its maximum extent above the POI at t = 60 ms. At this point no hydraulic jump is visible and no rope is yet formed. As the gravity forces the water downward, a ridge is formed at the top of the RFZ, which is carried by the momentum of the incoming liquid. The ridge thickens and moves slightly downwards under the action of the gravity force, and the vertical distance between the ridge and the POI decreases. The thickening process evolves until water eventually flows along the circumference and the rope flow is formed. At t = 150 ms the rope is partially evolved. The quasi-steady state is reached approximately 300 ms after impingement of the jet front and phase (ii) begins. This process has already been described in [23]. In the present case, the rope is so thick that the Rayleigh-Taylor instability is developed, leading to the formation of a bulge, which then drips form the rope (arrow at t = 540 ms). For continuous jet impingement the process repeats and causes frequent dripping of the liquid. At t = 500 ms the jet is turned off, but the water impinging at that point still spreads radially outwards until t = 540 ms. Then the wall film, which is left after the jet was turned off, begins to drain and phase (iii) starts. The liquid stored within the rope at the end of phase (ii), drains in form of a prominent wave. The wave passes the POI about 650 ms after the jet front impingement, leaving behind a thin, slowly flowing film. However, if the duration of the jet section (pulse) impingement phase, which depends on the pulsation frequency, is shorter than the time needed to reach the quasi-steady flow pattern, the phase (ii) will not be reached. Further, if the duration of intermission is sufficiently short, the draining wave does not pass the POI until the impingement of the next pulse. This implicates a collision between the spreading wall flow and the draining wave of the previous pulse. In Fig. 3b the flow patterns for the jet impingement at the pulsation frequency of f = 5Hz are presented. All other parameters are maintained the same as in Fig. 3a. It can be observed that the jet impinges below the draining wave, which was formed in phase (iii) of the previous pulse. During phase (i), at t = 26 ms the spreading wall flow collides with the draining wave, which decelerates the spreading of the former considerably. At t = 53 ms – 19 ms later than for f = 1Hz – the spreading wall flow reaches the edge of the heater. The maximum extent above the POI is reached at t = 100 ms, when the jet is turned off, and thus phase (ii) is not reached. The rope appears thinner. Draining starts at t = 130 ms and the draining wave reaches the upper edge of the heater at t = 175 ms. For both image series of Fig. 3, videos are provided in supplementary material 1 and 2. There, the circles mark the thermocouple positions for the heater oriented in the upward position and the brighter region marks the extent of the heater.

Fig. 3
figure 3

Image series showing the wall-flow pattern for a duty cycle of 50% and frequencies of a f = 1 Hz and b 5 Hz. The jet is turned off for time instants t > 500 ms respectively t > 100 ms. Bright area marks extent of heater. (Re = 31000, L/dN = 3)

3.1 Heat transfer and flow patterns

In the following, we first examine the phenomena governing heat transfer during pulsating jet impingement. Afterwards we contemplate the influence of pulsation on heat transfer efficiency in the frequency regime f = 1 − 5 Hz.

In Fig. 4, the measured time average temperature difference ∆T between water at the nozzle inlet and the wall is plotted versus the distance from the POI for different pulsation frequencies. In the following, this temperature difference will be referred to as the wall temperature. The wall temperatures are measured above (↑) and below (↓) the POI, and the nozzle-to-target distance is L/dN = 3. It can be seen that in case of the continuous jet ∆T is independent of the orientation.

Fig. 4
figure 4

Mean temperature difference between heated wall and liquid at the nozzle inlet for different pulsation frequencies (Hz) at the duty cycle 50%, as well as for continuous jet (DC = 100%). The upwards directed arrow denotes the temperatures measured with thermocouples located above the POI, and vice versa. ( Re = 31000, L/dN = 3)

Since the time-averaged mass flow rate of the impinging cooling liquid is reduced by 50% for the pulsating jet, ∆T increases. The temperatures at different locations strongly depend on the pulsation frequency, and in contrast to the continuous jets, they are significantly different for the regions above and below the POI. For f = 1 Hz the temperatures above are higher than below the POI. As was discussed in the context of the flow patterns presented in Fig. 3a, the former rope flows down the wall in a form of a wave, leaving behind a relatively thin and slow film. The regions above the POI are subject to this film for a longer period than regions below, which can be a reason of the lower heat transfer rate in this region. For f = 5 Hz, the wall temperatures above and below the POI are identical for r ≤ 36 mm, while they are slightly higher above the POI than below in the region r ≈ 40 − 56 mm. This is the region in which the collision between the spreading wall flow and the draining wave of the previous pulse is seen. The retardation of the spreading wall flow could be responsible for the lower heat transfer in this region.

In Fig. 5 the time-averaged wall temperature at different thermocouple positions is shown for Re = 59000. The data are presented for L/dN = 3 and for L/dN = 33. It can be seen that the wall temperature distributions for continuous jet impingement (f = 0 Hz) differ for different nozzle distances. While the wall temperatures are identical at the POI, the difference becomes significant at r = 16 mm. At r = 63 mm, the wall temperature is about 2 K (≈50%) higher for the nozzle distance L/dN = 33. As described in [6,7,8, 10, 11], a higher nozzle distance leads to an increase in the splattered mass fraction of water, ξ. The splattered liquid is ejected from the wall flow, and thus does not contribute to heat transfer. According to [6], the splattering takes place at the radial distance rs≈5.71dN ≈ 23 mm. This agrees well with the radial distance at which the temperatures measured for L/dN = 3 and for L/dN = 33 start to strongly deviate from each other. For discontinuous jet impingement, one case with f = 2 Hz and another case with f = 5 Hz are shown, also in Fig. 5. For f = 5 Hz, other than in Fig. 4, no difference between temperatures above and below POI is seen. The collision between spreading wall flow and draining wave takes place above and outside the heated region. Additionally, it can be seen that the wall temperatures are generally lower for f = 5 Hz than for f = 2 Hz. The only exception is at r = 63 mm above the POI. Since the provided mass flow rate is equal, it can be already seen that the heat transfer efficiency is increased for f = 5 Hz. In Fig. 6, three other cases for f = 2 Hz with different duty cycles are shown, while continuous jet impingement is kept for comparison. It can be seen that the wall temperatures are similar for both directions (above and below the POI) for r ≤ 48 mm.

Fig. 5
figure 5

Mean temperature difference between heated wall and liquid at the nozzle inlet for different pulsation frequencies (Hz) and duty cycles (%). (Re = 59000, L/dN = 3, 33)

Fig. 6
figure 6

Mean temperature difference between heated wall and liquid at the nozzle inlet for continuous and pulsating jet impingement. Pulsation with f = 2 Hz and different and duty cycles (%). (Re = 59000, L/dN = 3)

Only for r ≥ 56 mm the temperatures below the POI are higher than above. In order to rationalize this behavior, consider the wall temperature versus time plot presented in Fig. 7a. The curves are smoothed with a third-order smoothing spline in order to improve the visibility. As the jet is turned on at the beginning of each period and the liquid impinges the hot surface, the surface is cooled initially rapidly, whereas the rate of temperature decreasing slows down with the time. When the jet is turned off, the heat transport rate reduces and the wall temperature increases. It can be seen that the curves depicting the wall temperature evolution at a distance of 40 mm from the POI above and below this point are close to each other. However, the difference of temperatures above and below the POI is significant at larger distances from POI. In Fig. 7b a set of images is shown demonstrating the flow patterns at different time instants t after the impingement of the jet front for the parameters of Fig. 7a. These images cover one full cycle between two successive jet pulses. The circles mark the thermocouple positions above the POI. It can be seen that the spreading wall flow reaches the heater edge at t = 28 ms and its maximum spreading at 96 ms after impingement during phase (i). At 189 ms – shortly before the turn-off – a rope is formed, but phase (ii) is not reached, since a quasi-steady pattern is not yet established at the instant of the jet turn-off. After the turn-off the liquid from the rope starts flowing down as a wave. This wave passes the thermocouples located at 63 mm and 56 mm above the POI at a time instant around t=314 ms. At about this time, little dents are visible in the rising parts of the plots in Fig. 7a for data 56 and 63 mm above the POI (arrows). However, further downstream at r = 40 mm and at all the position below no such dents are visible. We believe that the liquid at the hydraulic jump located above the heater is cool, since the thermal boundary layer stays thin within the RFZ. When the wave forms and begins to flow down the wall, it contributes considerably to the cooling of the wall. Since the wall temperature sharply increases with increasing r in this region, the temperatures within the boundary layer in the wave could get higher than the wall temperature downstream, so that the wall, starting from some radial position, is not cooled by the wave flowing down. This effect can contribute to lower temperatures at the location 63 mm above the POI in comparison to the location 63 mm below the POI. It is noteworthy that the presented data for f = 2Hz in Fig. 6 are to some extent reversed to the data presented in Fig. 4 for f = 1Hz. However, the time span between the passing of the POI by the draining wave and the impingement of the next pulse, in which the heater is basically not cooled above the POI is considerably different. While the time span takes the value of about 350 ms for f = 1Hz, it takes the values of only about 120 ms for 2Hz and DC = 40%.

Fig. 7
figure 7

a Temperature difference (smoothed) between heated wall and liquid at the nozzle inlet at three distances above (↑) and below (↓) the POI. b image series showing the wall-flow pattern and the corresponding thermocouple positions (colors code). Bright area marks extent of heater. (Re = 59000, f = 2Hz, DC = 40%, L/dN = 3)

It can be observed that, as expected, the decrease in duty cycle and respectively of the average mass flow rate leads to increasing the wall temperature. At the same time, also the difference between the wall temperatures at the outer thermocouple positions above and below increases with decreasing duty cycle. Since the amount of water impinging during each period reduces accordingly, the share of heat transferred during phase (iii) with respect to the total heat transferred increases. How this increase relates to heat transfer efficiency will be discussed along Fig. 8 using the Stanton number.

Fig. 8
figure 8

Stanton number for Re = 59000 and different pulsation frequencies (Hz), and duty cycles (%). (L/dN = 3 and 33)

3.2 Heat transfer efficiency

In order to evaluate the heat transfer efficiency, the Stanton number introduced in Eq. (4) is plotted in Fig. 8 for selected data that has been presented in Figs. 5 and 6. The Stanton number is low in the center, where the thermal boundary layer is thin, and increases monotonically for pulsating flows, while a plateau is reached for continuous flow at r ≈ 48 mm. It can be seen that the Stanton numbers for all parameter sets at L/dN = 3 are close to each other, but higher duty cycles lead to higher Stanton numbers in the range of r = 24 to 48 mm. For r > 48 mm, lower duty cycles lead to higher Stanton numbers. Additionally, it can be seen that the difference between the Stanton numbers above and below the POI is highest for the lowest duty cycle. A possible explanation is the relative influence of the draining wave, which increases with lowering the duty cycle. Further, for a duty cycle of 33%, the jet has been turned on 167 ms and the rope flow – meaning the circumferential velocity within the rope – is not fully developed, while a considerable ridge is formed already. In this case, in relation to the mass that impinges within one period, a larger amount of water is located above the heater and provides cooling in phase (iii). In other words, the longer turn-on time for the higher duty cycles does not lead to larger amounts of water stored above the heater, and the excess water does not contribute to cooling in phase (iii). The continuous impinging jet at L/dN = 33 exhibits the lowest Stanton number for r ≥ 24 mm. This can be explained by a high splattered mass fraction for this parameter set (ξ=0.5), which does not contribute to heat transport.

The average Stanton number \( \overline{\mathrm{St}} \) provides a means for comparing the heat transfer efficiency of cases within a large range of parameter sets. In Fig. 9, the data for several Reynolds numbers and nozzle distances are compared. Note that Re = 20700, DC = 100 and Re = 41700, DC = 50 exhibit about equal mass flow rates. First, the results for L/dN = 3 will be discussed. Comparing only the results for Re = 41700, one can see that for a constant duty cycle, the Stanton number increases with increasing frequency, while for each frequency, the Stanton number increases with decreasing duty cycle. For the lowest duty cycle, f = 2 Hz and DC = 20%, the highest enhancement of 26% is reached in comparison to the same Reynolds number and continuous flow. While the efficiency is increased, cooling itself is reduced due to the decrease in the average mass flow rate to 20% and the mean wall temperature is about 59% higher. When compared to the same mass flow rate, e.g. Re = 41700, f = 5 Hz and Re = 20700 for the continuous flow, the enhancement is generally lower (about 12%). A comparison between f = 2 Hz and DC = 20% and continuous flow is not possible, since a jet with Re = 8300 corresponding to an average mass flow rate of 1.6 kg/min would not spread over the entire heater area, and a part of the heater cannot be cooled. Pulsation can therefore be used to cool a larger area using the same average mass flow rate.

Fig. 9
figure 9

Mean Stanton number for Re = 41,700 as well as further Reynolds numbers, for different pulsation frequencies (Hz) and duty cycles (%). (L/dN = 3, 33 and 167)

For L/dN = 33 the enhancement factors within Re = 41,700 remain as for L/dN = 3, but reduce to a maximum of 5% (20% for L/dN = 3) compared to Re = 31000. As mentioned above, this is caused by the increase of the splattered mass fraction, ξ, with increasing L/dN (ξ = 0, 0.35, 0.44 (0, 0.15, 0.4) for L/dN = 3, 33, 167 and Re = 41700 (Re = 31000) for continuous jet impingement [11]). For the highest nozzle distance L/dN = 167 the influence of pulsation is reduced. A possible reason is the growth of the jet front with growing nozzle distances (Fig. 10), which seems to exhibit a higher splattered mass fraction than the continuous part of the jet section. This would reduce the heat transfer for a certain amount of time after the jet section impinges, which would especially reduce the overall heat transfer of shorter pulses (high frequency and low duty cycle) and thereby explain the observed decrease.

Fig. 10
figure 10

Stitched images (procedure described in [11]) reconstructing the jet front for Re = 41,700, which increases in size with increasing nozzle distance L/dN = 3, 33 and 167 (a, b and c)

The influence of the splattered mass fraction becomes dominant for the cases summarized in Fig. 11. In this diagram, the average Stanton numbers for continuous and pulsating jet impingement experiments, characterized by the same average mass flow rate (Re = 31000, DC = 100 and Re = 59000, DC = 50), are compared with each other. If the mass flow rate stays identical, the pulsation leads to a reduction of the heat transfer efficiency for L/dN ≥ 33 due to a drastic increase of the splattered mass fraction with an increase of the nozzle distance for Re = 59000 (ξ = 0, 0.5, 0.48 for L/dN = 3, 33, 67, respectively). Additionally, it can be seen that the influence of pulsation is comparably low for the lowest nozzle distance. First, the heat transfer during jet impingement is higher than at lower Reynolds numbers and/or higher nozzle distances. Second, as can be observed in Fig. 7b, the wall flow spreads out far beyond the border of the heater. For higher nozzle distances (a higher rate of splattering) or lower Reynolds numbers, the extent of the RFZ reduces considerably (compare, [11, 24]).

Fig. 11
figure 11

Mean Stanton number for Re = 59,600 as well as further Reynolds numbers, for different pulsation frequencies (Hz) and duty cycles (%). (L/dN = 3, 33 and 67)

Assume that the mass of water accumulated in the rope is approximately similar for all cases. Then, the larger the RFZ, the lower is the share of the mass accumulated within the rope, which flows over the heater and cools it during phase (iii). The described influence is illustrated in Fig. 12, where the red lines span an angle of either 60° (L/dN = 3,left), or 71°(L/dN = 33,right). Both effects, the higher heat transfer rate during jet impingement and the smaller amount of water located above the heater, in relation to the impinged mass during one pulse, decrease the relative contribution of the draining wave to the overall heat transfer and thus reduce the effect imposed by pulsation.

Fig. 12
figure 12

Illustration of water above the heater for Re = 59,600 and L/dN = 3(left) and 33 (right)

Finally, and also related to the ratio of the sizes of the heater and the RFZ, it can be seen that for Re = 20700 a pulsation at the frequency of 1 Hz increases the heat transfer efficiency (see Fig. 9). For other Reynolds numbers, this was not the case due to the relatively long pause time of about 350 ms between the draining wave has passed the POI and the jet impingement of the next pulse, in which only little cooling is provided. However, for this setting the heat transfer efficiency is increased, which is due to a dewetting phenomenon, which will be addressed in the following section.

3.3 Pulsation and dewetting

In the case of impingement of smooth jets at low nozzle distances the rope above the POI can grow to a thickness which gives rise to the Rayleigh-Taylor instability leading to dripping of the liquid. During the thickening process, the weight of the rope flow increases, and thus, its distance from the POI reduces, since its weight has to be balanced by the wall-flow momentum, which was described at the beginning of section 3 (see also Fig. 3a and supplementary mat. 1). The consequence of the instability is illustrated in Fig. 13a for Re = 20700 and a nozzle distance L/dN = 3. During the experiment on the heater, it was visible that such an instability can lead to partial dewetting of the heater down to the region of the thermocouple at 56 mm above POI. Since the formed bulge suppresses the fresh water supply to regions above, the wall temperature increases. Thus, the temperature of the thin film above the bulge increases quickly, resulting in a strong temperature gradient along the radial coordinate, which can induce a Marangoni flow. This eventually leads to persisting dewetting of the heater and causes the temperature increase shown in Fig. 13b. The mean temperatures for the thermocouples at 40 mm (56 mm) exhibit 5.8 K (10.9 K) for continuous flow. For pulsation, the mean temperatures exhibit 12 K (17.8 K) for pulsation at the corresponding thermocouples, which inherits a factor near 0.5 and close to the duty cycle. However, it is seen at 63 mm above the POI that the wall temperature increases from 12 K to 18.2 K reaching almost 90% of the value (20.3 K) achieved with half the average mass flow rate over a time span of 15 s. For comparison, the time span between the build-up of the bulge and dripping amounts to 100 − 300 ms on the Plexiglas®. For pulsating jet impingement, the momentum of the spreading wall flow rewets the upper part of the heater in 29 of 30 cycles, and thus the entire heater is cooled. This example shows the power of pulsation to wet dry or to rewet dewetted regions. Therefore, using pulsating jet impingement could be beneficial in other related subjects, where dry patches can occur in the draining film below the POI, such as tank cleaning [10, 22], or in the cylindrical baffle of a feedwater deaerator [12].

Fig. 13
figure 13

Instability in the rope flow above the POI (a). Wall temperature for continuous (f = 0, DC = 100%, □) and pulsating jet impingement (f = 1 Hz, DC = 50%, ○) for selected thermocouple positions above the POI (b). (Re = 20700 and L/dN = 3 )

4 Conclusions

In this work, pulsating water jets impinging horizontally on a vertical wall have been investigated regarding their heat transfer efficiency and evaluated using the Stanton number. Pulsation in the investigated frequency regime induces complex wall-flow patterns, which can be subdivided into three phases. The spreading phase (i), a quasi-steady phase (ii), which only exists, if the jet is turned on sufficiently long, and the draining phase (iii). The latter phase is dominated by a wave, which is formed from the rope created in phases (i) and (ii). Increases in heat transfer efficiency for pulsating jets can be mainly assigned to the contribution of this draining wave to heat transfer. As the wave drains its temperature increases, and thereby its ability to cool decreases. Thus, the contribution of phase (iii) to heat transfer is constricted to the upper part of the heater. If the pause time is insufficiently long, the draining wave does not pass the POI during phase (iii) before the next pulse impinges. Then the spreading of the wall flow can be significantly decelerated, by a collision with the draining wave, which can reduce heat transfer during phase (i). However, the efficiency generally increases with increasing frequency and decreasing duty cycle.

Two cases have been distinguished in order to evaluate heat transfer efficiency:

First, a comparison within a set of parameters with equal Reynolds number [Eq. (3)], but different pulsation frequencies and duty cycles. The equal Reynolds number implies a comparable wetted area. In this case it was shown that the heat transfer efficiency can be increased up to 26% using pulsation, while the heat transport itself is – due to the reduced amount of cooling liquid – weakened. In addition, pulsation showed to be able to wet areas that were dewetted during continuous jet impingement.

Second, a constant mass flow rate. In the investigated regime of Re = 20700 − 59000, the splattered mass fraction is extremely depending on the Reynolds number for L/dN ≥ 17 [8, 11]. When comparing a pulsating jet with a continuous jet with the same mass flow rate, the Reynolds number – defined by the pulsation duty cycle – is higher, and the heat transferred to the draining wave is overcome by the generally lower heat transfer rate, due to increased splattering. In such cases, a reduction in efficiency was notified. Therefore, the use of pulsation should be constricted to low nozzle distances. Then, heat transfer efficiency could be increased by up to 12%. But pulsation can also be used to increase the cooling area with a set mass flow rate. In order to gain a deeper understanding of the underlying processes, the investigation of the hydrodynamics is necessary. Measuring the influence of pulsation on splattering as well as film thickness measurement – especially in the hydraulic-jump region – are part of ongoing work. It was also shown that pulsation could be more promising for smaller Reynolds numbers, in combination with smaller cooling areas.