An experimental study on spectroscopic analysis of alternating liquid dielectrics for transformer

  • Original Paper
  • Published:
Electrical Engineering Aims and scope Submit manuscript

Abstract

Conventionally, mineral oil impregnated with solid insulating materials has been used as an insulating medium in the transformers. On the other hand, mineral oil is less biodegradable than ester oils and it has poor fire-resistant characteristics. Therefore, the conventionally used mineral oils are not satisfying the new ecological requirements. Besides that the availability of fossil fuels is also going to run out. Consequently, several investigators have tried with different kinds of edible as well as non-edible oils for using them as liquid dielectrics in the transformers. This paper attempts to prove the feasibility of Pongamia pinnata oil (PPO) as an alternate liquid dielectric for transformer. At first, solid insulating material’s deterioration study was carried out using DGA, SEM, XRD and UV–Vis spectroscopy. Alongside, thermal stability of PPO and mineral oil was analyzed through FTIR spectroscopy. DGA results show that gas-generating phenomenon was found on both the oil samples. However, the generation of combustible gas in PPO impregnated with solid insulating material is found to be lower when compared with other oils. From the FTIR analysis, it is found that the structural difference between PPO and mineral oil is negligible. However, from XRD and UV–Vis spectroscopy, it is evident that depending on the type of material, the thus emitted spectra have different bandwidth and there is variation in the absorbance intensity. When the contamination rate is higher, the absorbance intensity of the insulating oil increased. SEM analysis shows that cellulose fiber’s width has drastically decreased in case of the solid insulation material immersed in mineral oil; also, there is evidence for bond breaking.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8

Similar content being viewed by others

Abbreviations

MO:

Mineral oil

PPO:

Mineral oil

IEC:

International Electrotechnical Commission

ASTM:

American Society for Testing and Materials

IEEE:

Institute of Electrical and Electronics Engineers

FTIR:

Fourier transform infrared spectroscopy

PPO:

Pongamia pinnata oil

DGA:

Dissolved gas analysis

H2 :

Hydrogen

CH4 :

Methane

C2H6 :

Ethane

C2H4 :

Ethylene

C2H2 :

Acetylene

CO:

Carbon monoxide

CO2 :

Carbon dioxide

TCG:

Total combustible gases

NA:

Not applicable

ND:

Not detectable

SEM:

Scanning electron microscope

XRD:

X-ray powder diffraction

UV–Vis:

Ultraviolet–visible spectroscopy

FKP:

Fresh kraft paper

AKPMO:

Aged kraft paper with mineral oil

AKPPO:

Aged kraft paper with Pongamia pinnata oil

FPB:

Fresh press board

APBMO:

Aged press board with mineral oil

APBPPO:

Aged press board with Pongamia pinnata oil

References

  1. Fofana I (2002) 50 years in the development of insulating liquids. IEEE Electr Insul Mag 29:13–25

    Article  Google Scholar 

  2. Fernández I, Ortiz A, Delgado F, Renedo C, Pérez S (2013) Comparative evaluation of alternative fluids for power transformers. Electric Power Syst Res 19:58–69

    Article  Google Scholar 

  3. Rouabeh J, M’barki L, Hammami, A, Jallouli I (2019) Studies of different types of insulating oils and their mixtures as an alternative to mineral oil for cooling power transformers. Heliyon 5:1–19

    Article  Google Scholar 

  4. Tokunaga J, Koide H, Mogami K, Hikosaka T (2016) Comparative studies on the aging of thermally upgraded paper insulation in palm fatty acid ester mineral oil and natural ester. IEEE Trans Dielectr Electr Insul 23:258–265

    Article  Google Scholar 

  5. George K, Frimpong OTV, Asano R (2011) Cellulose insulation in natural ester and mineral oil. IEEE Electr Insul Mag 27:36–48

    Google Scholar 

  6. Lundgaard LE, Hansen W, Ingebrigtsen S (2008) Ageing of mineral oil impregnated cellulose by acid catalysis. IEEE Trans Dielectr Electr Insul 15:540–546

    Article  Google Scholar 

  7. Mariprasath T, Kirubakaran V (2018) A real time study on condition monitoring of distribution transformer using thermal imager. Infrared Phys Technol 90:78–86

    Article  Google Scholar 

  8. Arshad M, Islam SM (2011) Significance of cellulose power transformer condition assessment. IEEE Trans Dielectr Electr Insul 18:1591–1598

    Article  Google Scholar 

  9. Lelekakis N, Guo W, Martin D, Wijaya J (2012) A field study of aging in paper–oil insulation systems. IEEE Electr Insul Mag 8:12–19

    Article  Google Scholar 

  10. Mandlik M, Ramu TS (2014) Moisture aided degradation of oil impregnated paper insulation in power transformers. IEEE Trans Dielectr Electr Insul 21:186–193

    Article  Google Scholar 

  11. Xiang R, Li S, Chen R, Li Y (2016) Effect of particle size of fly ash on the properties of lightweight insulation materials. Constr Build Mater 123:120–126

    Article  Google Scholar 

  12. Jia Z, Wang X, Lu H, Guan Z, Yang C (2015) Micro characterization and degradation mechanism of liquid silicone rubber used for external insulation. IEEE Trans Dielectr Electr Insul 22:313–321

    Article  Google Scholar 

  13. Wang M, Vandermaar AJ, Srivastava K (2002) Review of condition assessment of power transformers in service. IEEE Electr Insul Mag 18:12–25

    Article  Google Scholar 

  14. Raymon A, Karthik R (2015) Reclaiming aged transformer oil with activated bentonite and enhancing reclaimed and fresh transformer oil with antioxidants. IEEE Trans Dielectr Electr Insul 22:548–555

    Article  Google Scholar 

  15. de Farian H, Costa JGS, Olivas JLM (2015) A review of monitoring methods for predictive maintenance of electric power transformers based on dissolved gas analysis. Renew Sustain Energy Rev 46:201–209

    Article  Google Scholar 

  16. Cai S, Chen C, Guo H, Chen S, Zhou Z, Guo Z (2019) Fire resistance test of transformers filled with natural ester insulating liquid. J Eng 16:1560–1564

    Article  Google Scholar 

  17. Mariprasath T, Kirubakaran V (2016) A critical review on the characteristics of alternating liquid dielectrics and feasibility study on Pongamia pinnata oil as liquid dielectrics. Renew Sustain Energy Rev 65:784–799

    Article  Google Scholar 

  18. Hosier IL, Guushaa A, Westenbrink EW, Rogers C, Vaughan AS, Swingler SG (2011) Aging of biodegradable oils and assessment of their suitability for high voltage applications. IEEE Trans Dielectr Electr 18:728–738

    Article  Google Scholar 

  19. IEC IEC 6112560567 (2018) Test methods for oxidation stability—test method for evaluating the oxidation stability of insulating liquids in the delivered state oil-filled electrical equipment. Sampling of gases and of oil for analysis of free and dissolved gas guidance

  20. Augusta M, Martins G, Gomes AR (2012) Comparative study of the thermal degradation of synthetic and natural esters and mineral oil: effect of oil type in the thermal degradation of insulating kraft paper. IEEE Electr Insul Mag 28:22–28

    Google Scholar 

  21. Hembrom S (2013) Analysis of aged insulating oil for early detection of incipient fault inside the high voltage equipment. Dissertation National Institute of Technology

  22. Karthik R, Raja TSR, Sudhakar T (2013) Deterioration of solid insulation for thermal degradation of transformer oil. Cent Eur J Eng 3:226–232

    Google Scholar 

  23. Karthik R, Raja TSR, Shunmugam SS, Sudhakar T (2013) Performance evaluation of ester oil and mixed insulating fluids. J Inst Eng India Ser B 93:173–178

    Article  Google Scholar 

  24. Muhamad NA, Phung BT (2011) DGA for common transformer faults in soy seed-based oil. IET Electr Power Appl 5:133–142

    Article  Google Scholar 

  25. Karthick R (2014) Performance evaluation of transformer oil using UV–visible spectrometer. Acta Sci Technol 36:245–250

    Article  Google Scholar 

  26. Khan IU, Wang Z et al (2007) DGA of alternative fluids for power transformers. IEEE Electr Insul Mag 23:5–14

    Article  Google Scholar 

  27. Silverstein RM, Webster FX (2014) Spectrometric Identification of organic compounds. Wiley, New York

    Google Scholar 

  28. Vlachos N, Skopelitis Y, Psaroudaki M, Konstantinidou V, Chatzilazarou A, Tegou E (2006) Applications of Fourier transform-infrared spectroscopy to edible oils. Anal Chim Acta 573–574:459–465

    Article  Google Scholar 

  29. Suleiman AA, Muhamad NA, Bashir N, Murad NS, Arief YZ (2014) Effect of moisture on breakdown voltage and structure of palm based insulation oils. IEEE Trans Dielectr Electr Insul 21:2119–2126

    Article  Google Scholar 

  30. Atikah BJ (2014) Effect of long term thermal ageing on the performance of PFAE oil as a transformer oil. Dissertation UniversitiTeknologi

  31. Fofana I, Bouaïcha A, Farzaneh M (2011) Aging characterization of transformer oil—pressboard insulation using some modern diagnostic techniques. Euro Trans Electr Power 21:1110–1127

    Article  Google Scholar 

  32. Yan J, Liao R, Yang L, Li J, Liu B (2011) Product analysis of partial discharge damage to oil-impregnated insulation paper. Appl Surf Sci 257:5863–5870

    Article  Google Scholar 

  33. Liao R, Tang C, Yang L, Grzybowski S (2008) Thermal aging micro-scale analysis of power transformer pressboard. IEEE Trans Dielectr Electr Insul 15:1281–1286

    Article  Google Scholar 

  34. Wang S-Q, Zhang G-J, Wei J-L, Yang S, Dong M, Huang X-B (2010) Investigation on dielectric response characteristics of thermally aged insulating pressboard in vacuum and oil-impregnated ambient. IEEE Trans Dielectr Electr Insul 17:1853–1862

    Article  Google Scholar 

  35. Malik H, Singh S, Kr M, Jarial RK (2012) UV/VIS response based fuzzy logic for health assessment of transformer oil. Proc Eng 30:905–912

    Article  Google Scholar 

  36. Gomez NA, Abonia R, Cadavid H, Vargas IH (2011) Chemical and spectroscopic characterization of a vegetable oil used as dielectric coolant in distribution transformers. J Braz Chem Soc 22:2292

    Article  Google Scholar 

  37. Bakar NA, Abu-Siada A, Das N, Islam S (2013) Effect of conducting materials on UV–Vis spectral response characteristics. J Electr Electron Eng 1:81–86

    Google Scholar 

  38. Bagniuk J, Pawcenis D, Conte AM, Pulci O, Aksamit-Koperska M, Missori M, Łojewska J (2019) How to estimate cellulose condition in insulation transformers papers? Combined chromatographic and spectroscopic study. Polym Degrad Stab 168:1–14

    Article  Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to T. Mariprasath.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Mariprasath, T., Kirubakaran, V., Madichetty, S. et al. An experimental study on spectroscopic analysis of alternating liquid dielectrics for transformer. Electr Eng 103, 921–929 (2021). https://doi.org/10.1007/s00202-020-01136-x

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s00202-020-01136-x

Keywords

Navigation