Electrical Engineering

, Volume 100, Issue 3, pp 2147–2154 | Cite as

Mechanism research on active power fluctuation caused by steam turbine valve test

  • Jiasheng Wang
  • Qinfeng Ma
  • Jingliang Zhong
  • Xiaolong Gou
Original Paper
  • 62 Downloads

Abstract

To solve the problem of active power fluctuation and oscillation in the process of turbine’s throttle steam valve activity test, the mechanism and solutions were studied based on the real accident data from a thermal power unit. Theoretical analysis on the test control logic, valve actuator and valve flow characteristic was performed, and the results show that the main reason for the power fluctuation is the large deviation between actual valve flow characteristic and the designed one in the process of turbine’s throttle steam valve activity test. Moreover, the unreasonable control logic setting amplified the power fluctuation. After that, the reverse adjustment of primary frequency reset and power closed-loop control intensifies the fluctuation to power oscillation. The static and dynamic experiments both confirm that field test calibration of the valve flow characteristic is an effective way to reduce the active power fluctuation. Meanwhile, optimizing the control logic based on actuator’s characteristic and operation parameters can also relieve or even eliminate the power fluctuation and oscillation.

Keywords

Steam turbine Valve activity test Control logic Power fluctuation 

Notes

Acknowledgements

This work was supported by science and technology research projects of China Southern Power Grid Company Limited (No:066600KK5220120145; KK5220120128).

References

  1. 1.
    Lee S, Lee Y, Choi J (2014) Power supply assessment model of renewable energy generators focused on wind turbine generator and solar cell generator. J Int Council Electr Eng 4:302–308CrossRefGoogle Scholar
  2. 2.
    Bhuiyan FA, Yazdani A (2010) Reliability assessment of a wind-power system with integrated energy storage. Renew Power Gener IET 4:211–220CrossRefGoogle Scholar
  3. 3.
    Reddy SS (2017) Optimal power flow with renewable energy resources including storage. Electr Eng 39(2):685–695CrossRefGoogle Scholar
  4. 4.
    Qiu-hai GAO, Jian SHEN (2016) 600MW steam turbine valve abnormal activity test of analysis and processing. Electr Eng Technol 45(7):102–105 (in Chinese)Google Scholar
  5. 5.
    Wang J, Zhong J, Zhang J, Wang S (2016) Analysis and disposal of forced power oscillation in the transfer process of governor valve mode of turbine’s operation. Electr Power Compon Syst 41(4):185–192CrossRefGoogle Scholar
  6. 6.
    Kai S, Zhong Z, Nianguang Z, Xin X (2017) Modeling of steam turbine’s governing system during main steam valve activity test and its application. In: Chinese control conference (CCC), pp 2166–2171Google Scholar
  7. 7.
    Xia W (2014) Comprehensive optimization measures for unilateral joint valve activity test of high pressure total valve-governing valve of 600MW supercritical steam turbine. Guangdong Electr Power 27:23–27 (in Chinese)Google Scholar
  8. 8.
    Shuai ZUO, Zhiting ZHANG, Hongjun DAI, Nianjun CHEN (2015) Pro-control Strategy and Case Study on Risks in Valve Test of Siemens 1000 MW Steam Turbines. Electr Power 48:17–20 (in Chinese)Google Scholar
  9. 9.
    Wang X, Li X, Li F (2010) Analysis on oscillation in electro hydraulic regulating system of steam turbine. Exp Syst Appl 37:3887–3892CrossRefGoogle Scholar
  10. 10.
    Yang W, Yang J, Guo W, Norrlund P (2016) Response time for primary frequency control of hydroelectric generating unit. Int J Electr Power Energy Syst 74:16–24CrossRefGoogle Scholar
  11. 11.
    Victoire TAA, Jeyakumar AE (2005) Reserve constrained dynamic dispatch of units with valve-point effects. IEEE Trans Power Syst 20(3):1273–1282CrossRefGoogle Scholar
  12. 12.
    Rahmann C, Castillo A (2014) Fast frequency response capability of photovoltaic power plants: the necessity of new grid requirements and definitions. Energies 7:1–17CrossRefGoogle Scholar
  13. 13.
    Maffezzoni C (1997) Boiler-turbine dynamics in power-plant control. Control Eng Pract 5(3):301–312CrossRefGoogle Scholar
  14. 14.
    Alomoush MI (2010) Load frequency control and automatic generation control using fractional-order controllers. Electr Eng (Archiv fur Elektrotechnik) 91(7):357–368CrossRefGoogle Scholar
  15. 15.
    Halimi B, Suh KY (2012) Engineering nonlinearity characteristic compensation for commercial steam turbine control valve using linked MARS code and Matlab Simulink. Nucl Eng Des 243:360–370CrossRefGoogle Scholar
  16. 16.
    Nesbitt B (2007) Handbook of valves and actuators. Elsevier, New York, pp 193–213Google Scholar
  17. 17.
    Yang J (1994) Analysis of valve adjust characteristic in pipe. J Waterw Harb 3:29–34 (in Chinese)Google Scholar
  18. 18.
    Rogers G (2000) Power system oscillations. Springer, New York, pp 101–119CrossRefGoogle Scholar
  19. 19.
    Naghshbandy AH, Shanechi HM, Kazemi A, Pourfar I (2010) Study of fault location effect on the inter-area oscillations in stressed power systems using modal series method. Electr Eng 92(1):17–26CrossRefGoogle Scholar
  20. 20.
    Xiang-kun PANG, Chang-qing YAO, Xiang-rong MENG (2014) Reverse adjustment of primary/secondary frequency regulation. East China Electr Power 42:0558–1561 (in Chinese)Google Scholar
  21. 21.
    Restrepo JF, Galiana FD (2005) Unit commitment with primary frequency regulation constraints. IEEE Trans Power Syst 20:1836–1842CrossRefGoogle Scholar
  22. 22.
    Morita R, Inada F, Mori M, Tezuka K, Tsujimoto Y (2007) CFD simulations and experiments of flow fluctuations around a steam control valve. J Fluids Eng 129:48–54CrossRefGoogle Scholar

Copyright information

© Springer-Verlag GmbH Germany, part of Springer Nature 2018

Authors and Affiliations

  1. 1.School of Power EngineeringChongqing UniversityChongqingChina
  2. 2.Electric Power Dispatching Control Center of Guizhou Power Grid Co., LtdGuiyangChina
  3. 3.Electric Power Research Institute of Guizhou Power Grid Co., LtdGuiyangChina

Personalised recommendations