This article presents an algorithm for auto-reclosing of shunt compensated transmission lines. The algorithm uses signal analysis methods to estimate the future voltage shape over the circuit-breaker. Based on this voltage shape switching instants are estimated in the zero crossings. The minimization of the probability of a prearcing is reduced be adding time shift parameters. These parameters take the limited rise of strength recovery of the circuit breaker and the mutual influence of the coupling of the poles by a three-pole auto-reclosing into consideration. The advantage of the descript method is significant reduction of the switching overvoltage.

Zusammenfassung

Dieser Artikel beschreibt einen Algorithmus für die kontrollierte Wiedereinschaltung auf parallel-kompensierten Übertragungsleitungen. Der Algorithmus verwendet ein Signalanalyseverfahren zur Berechnung des zukünftigen Verlaufs der Spannung über dem Leistungsschalter. Mit Hilfe des berechneten Spannungsverlaufs ist eine Bestimmung von Nulldurchgängen als Einschaltzeitpunkte möglich. Die Wahrscheinlichkeit eines Vorüberschlages wird durch Addition eines Verschiebezeitparameters minimiert. Dieser Parameter berücksichtigt den Verlauf der Einschaltkennlinie des Leistungsschalters und die Beeinflussung der einzeinen Leiter untereinander bei einer dreipoligen automatischen Wiedereinschaltung. Der Vorteil des beschriebenen Verfahrens ist eine bedeutende Reduzierung der Schaltüberspannung.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  • Cho, K. B., Kim, J. B., Shim, J. B., Park, J. W. (1998): Development of an intelligent autoreclosing concept using Neuro-Fuzzy Technique — An optimal controlled switching for power system operations. CIGRE 1998, Session 13.

  • Froehlich, K., Hoelzl, C., Stanek, M., Carvalho, A. C., Hofbauer, W., Hoegg, P., Avent, B. L., Peelo, D. F., Sawada, J. H. (1997): Controlled closing on shunt reactor compensated transmission lines. I. Closing control device development. IEEE Transactions on Power Delivery, Vol. 12, Issue 2, April 1997: 734–740.

    Article  Google Scholar 

  • Lawrence Marple, S. (1987): Digital Spectral Analysis. London: Prentice Hall.

    Google Scholar 

  • Pilz, G., Schegner, P., Wallner, C. (2002): Analysis of noisy voltage signal with a high resolution of frequency for the closing of transmission lines. PSCC 2002, Sevilla.

  • Živanovič, R., Schegner, P., Seifert, O., Pilz, G.: Identification of the resonant-grounded system parameters by evaluating fault measurement records. IEEE Transactions on Power Delivery, submitted, accepted (will be published).

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to G. Pilz Dipl.-Ing..

Rights and permissions

Reprints and permissions

About this article

Cite this article

Pilz, G., Schegner, P., Wallner, C. et al. An algorithm for the three-pole controlled auto-reclosing of shunt compensated transmission lines with an optimization for the second and third pole. Elektrotech. Inftech. 121, 446–451 (2004). https://doi.org/10.1007/BF03055410

Download citation

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/BF03055410

Keywords

Schlüsselwörter

Navigation