Contents
Asymmetry of the supply voltage of a load and variation of its RMS value deteriorate supply quality, similarly as asymmetry of the load current, its reactive component, and variation of the current RMS value deteriorate loading quality. A method for adaptively improving the supply and loading quality with respect to the load unbalance and the voltage asymmetry is suggested and analyzed in this paper. The discussed method can be implemented for the development of an adaptive compensator for both the load balancing and supply voltage symmetrization. It was shown, moreover, that only three samples per periodT of two voltages and two currents are needed for generating the control signals for the adaptive operation of such a compensator.
Übersicht
Eine unsymmetrische Versorgungsspannung stört die Versorgungsqualität ähnlich wie ein unsymmetrischer Laststrom. In diesem Beitrag wird ein Verfahren zur adaptiven Verbesserung der Versorgungsqualität bezüglich Unsymmetrien der speisenden Spannung und der Lastschaltung vorgeschlagen und analysiert. Das Verfahren kann für die Entwicklung eines adaptiven Kompensators verwendet werden, der sowohl die Last als auch die Klemmenspannung symmetriert. Außerdem wird gezeigt, daß nur 3 Abtast-werte pro Periode bei je 2 Spannungen und Strömen ausreichen, um die Steuersignale für den adaptiven Betrieb eines solchen Kompensators zu erzeugen.
Similar content being viewed by others
References
Lyon, W. V.: Reactive power and unbalanced circuits. Electr. World (1920) 1419–1425
Buchholz, F.: Die Drehstrom-Scheinleistung bei ungleichmäßiger Belastung der drei Zweige. Licht und Kraft. Org. Elektrot., München, No. 2 (1922) 9–11
Quade, W.: Zusammensetzung der Wirk-, Blind- und Scheinleistung bei Wechselströmen beliebiger Kurvenform und neue Leistungsdefinitionen für unsymmetrische Mehrphasensysteme beliebiger Kurvenform. ETZ 58 (1937) 1312–1332
Nedelcu, V. N.: Die einheitliche Leistungstheorie der unsymmetrischen und mehrwelligen Mehrphasensysteme. ETZ-A 84 (1963) H. 5, 153–157
Nowomiejski, Z.; Cichowska, Z.: Unbalanced three-phase systems. Scientific Letters ‘Elektryka’ (in Polish) No. 17 (1964) 25–76
Depenbrock, M.: Blind- und Scheinlast in mehrphasig gespeisten Netzen. ETZ-A 86 (1965) 778–781
Harms, G.: Blindleistung im Energieeinsatz. Elektrotechnik, 62, H. 6 (1980) 20–22
Czarnecki, L. S.: Orthogonal decomposition of the current in a three-phase nonlinear asymmetrical circuit with nonsinusoidal voltage source. IEEE Trans. Instr. Meas. IM-37 (1988) 30–34
Schmitz, N. L.; Berndt, M. M.: Derating polyphase induction motors operating with unbalanced line voltages. IEEE Trans. Power App. Syst. 64 (1963) 680–686
Woll, R. F.: Effect of unbalanced voltage on the operation of polyphase induction motors. IEEE Trans. IA-11 (1977) 38–42
Yavamini, R.; Smith, W. J.: Third-harmonic current from unbalanced AC/DC converters. Proc. IEE, Vol. 130, Pt. C, No. 3 (1983) 96–106
Grandpierre, M.: Trannoy, B.: A static power device to rebalance and compensate reactive power in three phase network: Design and Control. Proc. of 1977 IAS Annual Conf., 127–135
Gyuagi, L.; Otto, R. A.; Putman, T. H.: Principles and applicationa of static thyristor-controlled shunt compensators. IEEE Trans. on Pow. App. and Syst. PAS-97 (1978) 1935–1945
Klinger, G.:L−C Kompensation und Symmetrierung für Mehrphasensysteme mit beliebigen Spannungsverlauf. ETZ-A (1979) H. 2, 57–61
Miller, T. J. E.: Reactive power control in electric systems. John Wiley & Sons, 1982
Vasu, E.; Rao, V. V. B.; Sankaran, P.: An optimization criterion for three phase reactive power compensation. IEEE Trans. PAS-104 (1985) 3216–3220
Mayer, D.; Pav, M.: A comment on nonliner 3-phase system compensation. Electr. Obzor (in Czech) 77 (1988) cis. 2, 75–77
Czarnecki, L. S.: Reactive and unbalanced currents compensation in three-phase asymmetrical circuits under nonsinusoidal condition. IEEE Trans. IM-38 (1989) 754–759
Czarnecki, L. S.: Minimization of unbalanced and reactive currents in three-phase asymmetrical circuits with nonsinusoidal voltage. Proc. IEE Pt.B, Vol. 139, No. 4 (1992) 347–354
Willems, J. L.: The compensation of reactive and unbalanced currents in 3-phase systems. European Trans. on Electrical Power Engineering ETEP 3, No. 1 (1993) 61–66
Haque, S. E.; Malik, N. H.; Shepherd, W.: Operation of a fixed capacitor-thyristor controlled reactor (FC-TCR) power compensator. IEEE Trans. on Pow. App. and Syst. PAS-104 (1985) 1385–1390
Czarnecki, L. S.: Two algorithms of the fundamental harmonic complex RMS value calculation. Arch. Elektrotech. 75 (1992) 163–168
Author information
Authors and Affiliations
Rights and permissions
About this article
Cite this article
Czarnecki, L.S. Supply and loading quality improvement in sinusoidal power systems with unbalanced loads supplied with asymmetrical voltage. Archiv f. Elektrotechnik 77, 169–177 (1994). https://doi.org/10.1007/BF01573892
Received:
Issue Date:
DOI: https://doi.org/10.1007/BF01573892