Microprocessor-based diagnostic device for protecting the generator-transformer unit from a single-phase ground fault

  • From Ideas to their Implementation
  • Published:
Hydrotechnical Construction Aims and scope

Conclusions

  1. 1.

    A microprocessor-based device was developed for checking (measuring) the level of the insulation resistance of the stator winding of a unit in the range 0.5–500 MΩ and absorption coefficient in the range 1–10 with output of the measurement results to a digital indicator.

  2. 2.

    All measurements are taken on a stopped or operating unit in a semiautomatic regime after pushing a button on the face panel of the device. It is possible to use the device as part of a process control system or in a diagnostic system with automatic control from a computer.

  3. 3.

    The device underwent a check on the units of the Skhodnya and Chirkey hydrostations, where it showed good results. It is suggested that it be introduced.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

Literature cited

  1. P. T. Anokhin, A. A. Finkel', “Protection from ground faults and check of the insulation of a generator stator winding,” Elek. Stan., No. 7, (1973).

  2. V. N. Vavin, Protective Relays of Turbine Generator-Transformer Units [in Russian], Énergoizdat, Moscow (1982).

    Google Scholar 

  3. V. M. Kutin, A. V. Kobylyanskii, O. I. Kul'matitskii, and A. P. Kunash, “Improvement of the means of protection from single-phase ground faults in the generator-transformer unit,” Elek. Stan., No. 4 (1986).

  4. V. B. Kulakovskii, Preventive Tests and Defects of Insulation of Large Electric Machines [in Russian], Énergiya, Moscow (1970).

    Google Scholar 

  5. A. M. Karpov, T. M. Memeni, V. N. Rusinov, et al., “Device for protecting the stator of an electric machine from ground faults,” USSR Author's Certificates 980205 and 955323, Otkr. Izobr., No. 45 (1982).

Download references

Authors

Additional information

Translated from Gidrotekhnicheskoe Stroitel'stvo, No. 9, pp. 43–45, September, 1989.

Rights and permissions

Reprints and permissions

About this article

Cite this article

Némeni, T.M., Panteleev, A.M., Krasil'nikov, A.M. et al. Microprocessor-based diagnostic device for protecting the generator-transformer unit from a single-phase ground fault. Hydrotechnical Construction 23, 549–552 (1989). https://doi.org/10.1007/BF01432067

Download citation

  • Issue Date:

  • DOI: https://doi.org/10.1007/BF01432067

Keywords

Navigation