Abstract
Adaptation of amoebae to four cooling tower Biocides, which included a thiocarbamate compound, tributyltin neodecanoate mixed with quaternary ammonium compounds (TBT/QAC), another QAC alone, and an isothiazolin derivative, was studied. Previously we found that amoebae isolated from waters of cooling towers were more resistant to cooling tower biocides than amoebae from other habitats. Acanthamoeba hatchetti and Cochliopodium bilimbosum, obtained from American Type Culture Collection and used in the previous studies, were tested to determine whether they could adapt to cooling tower Biocides. A. hatchetti was preexposed to subinhibitory concentrations of the four Biocides for 72h, after which they were tested for their resistance to the same and other biocides. C. bilimbosum was exposed to only two biocides, as exposure to the other two was lethal after 72 h. Preexposure to the subinhibitory concentrations of the Biocides increased the resistance of the amoebae, as indicated by a significant increase in the minimum inhibitory concentration (up to 30-fold). In addition, cross-resistance was also observed, i.e., exposure to one biocide caused resistance to other biocides. These results show that amoebae can adapt to biocides in a short time. The phenomenon of cross-resistance indicates that regularly alternating biocides, as is done to control microbial growth in cooling towers, may not be effective in keeping amoeba populations in check. On the contrary, exposure to one biocide may boost the amoebae's resistance to a second biocide before the second biocide is used in the cooling tower. Since amoebae may harbor Legionella, or alone cause human diseases, these results may be important in designing effective strategies for controlling pathogens in cooling towers.
References
Anand CM, Skinner AR, Malic A, Kurtz JB (1983) Interaction of L. pneumophila and a free living amoeba (Acanthamoeba palestinensis). J Hyg Camb. 91:167–178
Barbaree JM, Fields BS, Freely JC, Gorman GW, Martin WT (1986) Isolation of protozoa from water associated with a legionellosis outbreak and demonstration of intracellular multiplication of Legionella pneumophila. Appl Environ Microbiol 51:422–424
Barker J, Brown MRW, Collier PJ, Farrell I, Gilbert P (1992) Relationship between Legionella pneumophila and Acanthamoeba polyphaga: physiological status and susceptibility to chemical inactivation. Appl Environ Microbiol 58:2420–2425
Broadbent CR (1993) Legionella in cooling towers: practical research, design, treatment, and control guidelines. In: Barbaree JM, Breiman RF, Dufour AP (eds) Legionella: current status and emerging perspectives. American Society of Microbiology, Washington, DC, pp 217–222
Brozel VS, Cleote TE (1991) Resistance of bacteria from cooling waters to bactericides. J Ind Microbiol 8:273–276
Domingue EL, Tyndall RL, Mayberry WR, Pancorbo OC (1988) Effects of three oxidizing biocides on Legionella pneumophila serogroup 1. Appl Environ Microbiol 54:741–747
Dondero TJ, Rendtroff RC, Mallison GF, Weeks RM, Levy JS, Wong EW, Schaffner W (1980) An outbreak of Legionnaires' disease associated with a contaminated air-conditioning cooling tower. N Engl J Med 302:365–370
Elsmore R (1993) Microbiocides and control of Legionella. In: Barbaree JM, Breiman RF, Dufour AP (eds) Legionella: current status and emerging perspectives. American Society of Microbiology, Washington, DC, pp 250–253
Fields BS, Sanden GN, Barbaree JM, Morill WE, Wadowsky RM, White EH, Feeley JC (1989) Intracellular multiplication of Legionella pneumophila in amoebae isolated from hospital hot water tanks. Curr Microbiol 18:131–137
Fliermans CB, Cherry WB, Orrison LH, Smith SJ, Tison DL, Pope DH (1981) Ecological distribution of Legionella pneumophila. Appl Environ Microbiol 41:9–16
Grace RD, Dewar NE, Barnes WG, Glenn RH (1981) Susceptibility of Legionella pneumophila to three cooling tower microbiocides. Appl Environ Microbiol 41:233–236
Gulley DD, Boelter AM, Bergman HL (1988) Toxstat release 2.1. Fish Physiology and Toxicology Laboratory, University of Wyoming, Laramie, Wy.
Holden EP, Winkler HH, Wood DO, Leinbach ED (1984) Intracellular growth of Legionella pneumophila within Acanthamoeba castelland. Neff. Infect. Immun 45:18–24
Johnson JD (1978) Measurement and persistence of chloride residuals in natural waters. In: Jolley RL (ed) Water chlorination, vol. I. Ann Arbor Science, Ann Arbor, Mich., pp 41–63
Kilvington S (1990) Activity of water biocide chemicals and contact lens disinfectants on pathogenic free-living amoebae. Int Biodeter 26:127–138
Kilvington S, Price J (1990) Survival of Legionella pneumophila within cysts of Acanthamoeba polyphaga following chlorine exposure. J Appl Bacteriol 68:519–525
King CH, Shorts EB, Wooley RE, Porter KG (1988) Survival of coliforms and bacterial pathogens within protozoa during chlorination. Appl Environ Microbiol 54:3023–3033
Kurtz JB, Bartlett CLR, Newton UA, White RA, Jones NL (1982) Legionella pneumophila in cooling water systems. J Hyg Camb. 88:369–381
Negron-Alvira A, Perez-Suarez I, Hazen TC (1988) Legionella spp. in Puerto Rico cooling towers. Appl Environ Microbiol 54:2331–2334
Newsome AL, Baker RL, Miller RD, Arnold RR (1985) Interactions between Naegleria fowleri and Legionella pneumophila. Infect Immun 50:449–452
Page FC (1976) An illustrated key to freshwater and soil amoebae. (Freshwater Biological Association Scientific Publication No. 34) Freshwater Biological Association, Ambleside, England
Paszko-Kolva C, Yamamoto H, Shahamat M, Sawyer TK, Morris G, Colwell RR (1991) Isolation of amoebae and Pseudomonas and Legionella spp. from eyewash stations. Appl Environ Microbiol 57:163–167
Rowbotham TJ (1980) Preliminary report on the pathogenicity of Legionella pneumophila for freshwater and soil amoebae. J Clin Pathol 33:1179–1183
Shelton BG, Morris GK, Gormon GW (1993) Reducing risks associated with Legionella bacteria in building water systems. In: Barbaree JM, Breiman RF, Dufour AP (eds) Legionella: current status and emerging perspectives. American Society of Microbiology, Washington, DC, pp 279–281
Srikanth S, Berk SG (1993) Stimulatory effect of cooling tower biocides on amoebae. Appl Environ Microbiol 59:3245–3249
Wadowsky RM, Butler LJ, Cook MK, Verma SM, Paul MA, Fields BS, Keleti G, Sycora JL, Yee RB (1988) Growth supporting activity for Legionella pneumophila in tap water cultures and implication of Hartmanellid amoebae as growth factors. Appl Environ Microbiol 54:2677–2682
Wright JB, Ruseska I, Costerton JW (1991) Decreased biocide susceptibility of adherent Legionella pneumophila. J Appl Bacteriol 71:531–538
Yamamoto H, Sugiura M, Kusunoki S, Ezaki T, Ikedo M, Yabuuchi E (1992) Factors stimulating propagation of Legionellae in cooling tower water. Appl Environ Microbiol 58:1394–1397
Author information
Authors and Affiliations
Additional information
Correspondence to: S.G. Berk.
Rights and permissions
About this article
Cite this article
Srikanth, S., Berk, S. Adaptation of amoebae to cooling tower biocides. Microb Ecol 27, 293–301 (1994). https://doi.org/10.1007/BF00182412
Received:
Revised:
Issue Date:
DOI: https://doi.org/10.1007/BF00182412