Changes in the concentration of volatile organic compounds and aldehydes in newly constructed houses over time

  • N. SuzukiEmail author
  • H. Nakaoka
  • Y. Nakayama
  • K. Takaya
  • K. Tsumura
  • M. Hanazato
  • S. Tanaka
  • K. Matsushita
  • R. Iwayama
  • C. Mori
Open Access
Original Paper
  • 19 Downloads

Abstract

Nowadays, people spend most of their time indoors; thus, the indoor environment greatly affects human health because of exposure to chemicals indoors. Thus, in collaboration with Japanese house builders, a list of building materials having low volatile organic compound concentrations was compiled herein. The air-quality samples from seven newly built houses (seven bedrooms and seven living rooms) were collected and tested for 64 volatile organic compounds and two aldehydes. Air samples were obtained from the house with no furniture or household goods and were sampled 1 week after construction and repeated after a month. Furthermore, the test results with a 2009 survey of indoor air quality in newly constructed houses were compared. One week after construction, the xylene, styrene, toluene, formaldehyde, and ethylbenzene concentrations were less than half the standard guideline values set in Japan. The main substances detected in the samples were 2-butanone, acetone, ethanol, ethyl acetate, butyl acetate, and undecane. The statistical significance of the changes in substance concentrations over time was examined via Wilcoxon signed-rank test. One month after construction, the concentrations of all chemical substances had undergone a statistically significant reduction, except butyl acetate. The median of total volatile organic compounds in living rooms was 291 µg/m3, and the maximum was 354 µg/m3; both were under Japan’s provisional total volatile organic compound target of 400 µg/m3. These values were significantly lower than those recorded by other researchers. This study concludes that using experimentally identified low volatile organic compound materials effectively improves the indoor air quality.

Keywords

Environmental preventive medicine Indoor air quality Sick building syndrome Total volatile organic compounds 

Introduction

With recent technological developments, houses are now constructed to be more energy efficient and new construction emphasizes airtightness and heat insulation. Improved airtightness and heat insulation has had the unexpected consequence that the volatile organic compounds (VOCs) that are emitted from interior materials and buildings probably circulate within the room, which deteriorates the indoor air quality (IAQ). Indoor concentrations of VOCs generally exceed the concentrations outdoors (Begerow et al. 1995; Shields et al. 1996). On average, people spend ~ 90% of their time indoors in a day (Klepeis et al. 2001). Therefore, IAQ has a great effect on human health.

VOCs have been suspected as one of the major causes of the symptoms that are grouped together as “sick building syndrome” such as fatigue, asthmatic symptoms, eye and mucous-membrane irritation, and headache (Norbäck et al. 1995; Wieslander et al. 1997; Wolkoff et al. 1998; Seife 1999; Norbäck et al. 2000; Wolkoff and Nielsen 2001; Cox et al. 2002; Mølhave 2003; Katsoyiannis et al. 2008; Herberth et al. 2009; Heinrich 2011; Mori and Todaka 2011; Azuma et al. 2016). Reducing the volatile compounds in indoor atmospheres is an important step in preventing these symptoms. Therefore, governing bodies including the World Health Organization have instituted guideline concentrations for several VOCs in indoor air. Many national building codes also state that new houses and building must have safe and healthy IAQ (Japanese Ministry of Health Lab and Welf 1997; Finland’s Ministry of the Environment 2002; The Swedish National Board of Housing, Building and Planning and Boverket 2002; Ministry of Transport Building and Housing of Denmark 2018).

Several studies have focused on the IAQ of newly built buildings and its change over time (Seifert 1992; Wolkoff 1999; Scholz and Santl 1999; Bornehag and Stridh 2000; Rehwagen et al. 2003; Raw et al. 2004; Järnström et al. 2006). These studies indicate that the concentrations of VOCs in the indoor air of newly built buildings are much higher than the guideline values specified by each country, and Holøs et al. (2019) indicated that the off-gassing phase would last at least 2 years. However, Tuomainen et al. (2001) showed that VOC concentrations in new houses constructed using low-emitting materials could be reduced by ventilating the houses for 1 week, and Noguchi et al. (2016) also concluded that operating the ventilation system for 3 months would effectively reduce VOCs in newly constructed buildings. Herein, in cooperation with a residential building company, we investigated whether the IAQ of seven newly built houses, constructed using low-emission materials, could achieve good air quality; we also noted how much the VOC concentration decreases over time, specifically after 1 week and 1 month of the construction. This study first identified the following five compounds: styrene, formaldehyde, ethylbenzene, toluene, and xylene, which are mentioned in “Housing Quality Assurance Act” by the Japanese Ministry of Land, Infrastructure, Transport, and Tourism; this act was enacted to promote quality housing construction. Then, we checked the concentration values of the six most abundant substances and the TVOC to compare our results with that of another study.

As preliminary tests, the emission rates of these scheduled compounds from building materials (flooring, wallpaper, and substrate panel) were measured in a small test chamber, and low-emission materials were selected and used for the construction of the houses.

Indoor airborne chemicals are emitted not only from construction materials but also from furniture, household goods, and personal care products. Therefore, to evaluate the effect of construction materials on IAQ, measurements must be taken before furniture and household goods are brought into the rooms. Conversely, once construction is completed, houses are typically handed over to the owner in short order. Some studies have sampled the air in newly built houses before delivery, but few studies have taken measurements of the same house at two different times, without the influence of furniture and household goods. It is difficult to measure indoor air chemicals in newly built houses in the same situation at different times, and no studies which compare those results were found. Thus, seven newly built houses (seven bedrooms and seven living rooms) for 64 VOCs and two aldehydes were checked at different times and compared in this study. These measurements were performed together with records of temperature and humidity, and samples were collected within 1 week of the end of construction and again 1 month later. None of the homes had furniture and household goods inside during the 1-month period between samples. For the sake of this research, the move-in dates were delayed by 1 month after completion, in cooperation with the house owners.

The houses measured in this study were built in and around Tokyo by a single residential building firm. Seven houses were chosen from houses built by this firm between March 2016 and February 2017. The data were collected between March 2016 and March 2017 and were analyzed at the Center for Preventive Medical Sciences, Chiba University, and MC Evolve Technologies Corporation. The present study, referred to as IAQ-S 2015 below, is also compared with data from a study of newly built houses in Japan conducted by Onuki A et al. in 2009 (IAQ-S 2009) to gain insight into the characteristics of IAQ in newly built houses at these times (Onuki et al. 2009).

Materials and methods

Characteristics of houses

The owners of these houses were asked for permission to measure the levels of VOCs and aldehydes in indoor air shortly after construction, with completion judged as the last finishing nailing. The targeted houses were all framed with light-gage steel. Wood floors (solid wood, painted finish, and sheet finish) were installed in all rooms. All walls were either covered with wallpaper or applied with starch adhesives.

Indoor air sampling and analysis

Herein, measurements based on “Standard methods of air sampling and measurement” issued by the Ministry of Health, Labour and Welfare of Japan (MHLW 2000) were performed. All windows and doors were left open for 30 min for ventilation before collecting the air samples; all open doors and windows were closed for > 5 h. Air samples were then collected from the living rooms and bedrooms of the houses via active sampling for 30 min using the apparatus shown in Fig. 1. The rooms’ ventilation systems were engaged, and their air conditioning units were turned off while collecting the samples. The environmental factors of temperature and humidity were recorded. These samples quantified 64 VOCs and two aldehydes (Table 1). We conducted the sampling and analysis according to ISO 17025, and HPLC analysis and GC/MS analysis were performed according to ISO16000-3 and ISO16000-6, respectively.
Fig. 1

Equipment setup used for active sampling a living room and b bedroom

Table 1

List of analyzed aldehydes and VOCs

64 VOCs

2 aldehydes

2-Propanol

2-Butoxyethanol

Formaldehyde

Pentane

Nonane

Acetaldehyde

Ethyl acetate

Tricyclene

 

Dichloromethane

α-Pinene

 

1-Propanol

3-Ethyltoluene

 

Ethyl acetate

Camphene

 

Hexane

4-Ethyltoluene

 

Chloroform

1,3,5-Trimethylbenzene

 

1,2-Dichloroethane

2-Ethyltoluene

 

2,4-Dimethylpentane

β-Pinene

 

1,1,1-Trichloroethane

1,2,4-Trimethylbenzene

 

Butanol

D4

 

Benzene

Decane

 

Carbon tetrachloride

Isododecane

 

Cyclohexane

p-dichlorobenzene

 

1,2-Dichloropropane

2-Ethyl-1-hexanol

 

Bromodichloromethane

3-Carene

 

Trichloroethylene

1,2,3-Trimethylbenzene

 

Isooctane

p-Cymene

 

Heptane

Limonene

 

4-Methyl-2-pentanone(MIBK)

4-Ethyl-1,2-dimethylbenzene

 

Methylcyclohexane

Undecane

 

Toluene

1,2,4,5-Tetramethylbenzene

 

Dibromochloromethane

D5

 

Butyl acetate

Dodecane

 

Octane

Tridecane

 

Tetrachloroethylene

D6

 

Ethylbenzene

Texanol

 

m, p- xylene

Tetradecane

 

Styrene

Pentadecane

 

Acetone

2-Butanone

 

o- xylene

Hexadecane

 

VOCs

Tenax-TA® (porous polymer resin based on 2,6-diphenylene oxide), purchased from Sigma-Aldrich, was used for active sampling of VOCs. These tubes were pumped with the sampled air at 100-mL/min flow rate for 30-min collection period. The air samples were analyzed after collection using an Agilent 6890 gas chromatograph (Agilent Technologies Inc.) equipped with a TurboMatrix ATD unit (PerkinElmer, Inc.) and an Agilent MSD 5973 N quadrupole mass spectrometer. The Tenax-TA was heated at 260 °C for 10 min for thermal desorption. The transfer-line temperature and split ratio were 220 °C and 7:1, respectively. The gases were separated for 2 min using HP-VOC columns (60 m × 0.32 mm; inner diameter 1.8 µm) (Agilent Technologies Inc.) at 35 °C. Columns were first heated to 95 °C at 15 °C/min. These were then heated to 105 °C at 2.5 °C/min. Columns were finally heated to 250 °C at 5 °C/min. As the carrier gas, helium (purity > 99.9999%) was used for chromatography; it was then flowed into the column at 3.0 mL min−1. Recovery rates of toluene, ethylbenzene, xylene, styrene, and tetradecane in Tenax-TA was 96~106 (%). The identified VOCs were quantified in scan mode (at mass-to-charge, or m/z, ratios of 35–550). Each compound’s standard substance was used for determining the 64 VOCs’ concentration levels. As the toluene equivalent of all substances, TVOC was calculated with carbon lengths from C6 (n-hexane) to C16 (hexadecane).

Aldehydes

2,4-Dinitrophenylhydrazine (DNPH) cartridges that were designed for ketones and aldehydes (GL Sciences Inc.) were used for aldehyde measurements. Measurements were conducted at a pump flow rate of 1.0 L/min for the collection period of 30 min. The gas tube was eluted after sampling using a syringe containing 10 mL of acetonitrile at a flow rate of 2–5 mL/min. The volume was set to 5.0 mL for high-performance liquid chromatography (HPLC); the analysis was conducted using HPLC Agilent 1260 Infinity LC from Agilent Technologies. Inertsil ODS-SP columns (250 × 4.6 mm2; internal diameter 5.0 µm) from GL Sciences were used for separation, with a column oven temperature of 40 °C and an injection volume of 10 µL. A mixed solution containing acetonitrile and water was the mobile phase; 1.0 mL/min was the column flow rate. Acetonitrile/water solution (52:48 mixing ratio) was flowed for 15 min followed by acetonitrile/water (mixing ratio 52:48) for 20 min, and then acetonitrile/water (mixing ratio 75:25) for 23 min. Concentration levels of two compounds were calculated using the standard substance of each compound. Recovery rates of formaldehyde and acetaldehyde in DNPH cartridge was 101~105 (%).

Emission rate test

In a chamber of 20 L, the emission rate tests were conducted using the small-chamber method published in JIS A 1901 (Ministry of Land, Infrastructure, Transport and Tourism and JIS 2015), which is based on ISO 16000-9. The test conditions were adjusted to obtain the desired test temperature, relative humidity, ventilation frequency, and test loading rate of 28 °C, 50%, 0.5 times/h, and 2.25 m2/m3, respectively. The emission rates for the two aldehydes and 64 VOCs were measured on the seventh day after confining the plates in the small chamber.

Statistical analysis

The Wilcoxon signed-rank test was performed on all data to determine whether the concentration of chemical substances had undergone a statistically significant change over the month after measurements conducted by us. All analyses were conducted using the IBM SPSS Statistics package, version 24. A statistically significant result of p values < 0.05 was considered.

Results and discussion

Indoor environment characteristics

Table 2 shows the median and maximum temperatures and relative humidity levels in the indoor environments.
Table 2

Indoor environments

 

Living room

Bed room

 

Within 1 week after completion

1 month later

Within 1 week after completion

1 month later

 

Median

Max

Median

Max

Median

Max

Median

Max

Temperature (°C)

13.8

20.5

16.5

30.2

13.5

15.8

15.5

27.6

Relative humidity (%)

57

68

51

70

52

78

52

74

Within 1 week after construction, the temperatures of the living rooms were in the range 12.0–20.5 °C with a mean ± SD of 13.9 °C ± 3.8 °C, and the bedroom temperatures were in the range 11.5–15.8 °C with a mean ± SD of 13.6 °C ± 1.6 °C. One month after construction, the temperatures of the living rooms were in the range 12.2–30.2 °C with a mean ± SD of 17.5 °C ± 8.5 °C, and the bedroom temperatures were in the range 11.9–27.6 °C with a mean ± SD of 16.7 °C ± 6.9 °C.

The humidity range in the living rooms for the first measurement was 48–68% with a mean ± SD of 51.3% ± 7.9% and that in the bedrooms was 47–78% with a mean ± SD of 55.8% ± 12.6%. One month after construction, the humidity range in the living rooms was 42–70% with a mean ± SD of 53.5% ± 12.0% and that in the bedrooms was 44–76% with a mean ± SD of 57.9% ± 11.1%.

Table 3 shows the median and maximum values of the five substances listed in the Japanese “Housing Quality Assurance Act,” as measured in the present study, listed along with the data from IAQ-S 2009 for comparison.
Table 3

Changes in the concentrations of five regulated compounds

Compounds

Guideline valuec (μg/m3)

IAQ-S 2015a living room (7 rooms)

IAQ-S 2015 Bed room (7 rooms)

IAQ-S 2009b

(25 rooms)

Within 1 week after completion

1 month later

Within 1 week after completion

1 month later

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Formaldehyde

100

8.2

17.2

4.9

8.9

7.1

17.6

3.5

8.9

16

130

Toluene

260

19.5

84.4

10.2

20.8

5.2

81.3

4.3

47.6

30

359

Xylene

870

1.8

7.0

1.5

5.4

1.7

7.1

1.2

13

18

272

Ethylbenzene

3800

2.4

7.7

1.5

6.3

2.3

7.7

1.1

18.3

13

552

Styrene

220

2.9

4.2

1.3

3.7

1.0

1.1

NDd

ND

5.9

1430

aIAQ-S 2015: Survey of the indoor air quality (IAQ) in newly constructed houses 2015

bIAQ-S 2009: Trends in high-concentration indoor air chemicals detected in newly constructed houses (Onuki et al. 2009)

cThese five substances are described in the Japanese law about the promotion of quality assurance in housing

dND:Not Detected

Table 4 lists the median and maximum concentrations of the six most abundant substances and the TVOC, along with data from IAQ-S 2009. At 1 month after the construction, TVOC had a median value of 291 μg/m3 and a maximum of 354 μg/m3 in the living room, and a median value of 189 μg/m3 and a maximum of 310 μg/m3 in the bedroom; these results confirm that the houses met the TVOC target of 400 μg/m3 in Japan. These concentrations were also much lower than those recorded in IAQ-S 2009.
Table 4

Concentrations of the six most abundant substances and the TVOC of IAQ-S 2015 and IAQ-S 2009

 Compoundsc

Guideline value (μg/m3)

IAQ-S 2015a living room (7 rooms)

IAQ-S 2015 Bed room (7 rooms)

IAQ-S 2009b

(25 rooms)

Within 1 week after completion

1 month later

Within 1 week after completion

1 month later

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

Median (μg/m3)

Max (μg/m3)

2-Butanone

34.6

99

19.8

21.3

17.3

107

9.0

19.8

20.5

635

Acetone

17.2

46.8

11.4

16.6

12

18

14.0

18.0

55.1

616

Ethanol

20.4

37.3

9.5

29.3

14.6

23.8

8.9

12.0

20

578

Ethyl acetate

18.6

33.7

30.7

61.8

11.2

93.1

10.6

31.2

13.3

121

Butyl acetate

22.9

27.6

8.5

27.4

7.2

105

5.5

6.4

11.2

64.3

Undecane

15.2

26.1

7.2

20.9

7.6

24.1

4.7

20.9

11.3

164

TVOCd

 

550

591

291

354

217

614

189

310

1280

12100

aIAQ-S 2015: Survey of the IAQ in newly constructed houses 2015

bIAQ-S 2009: Trends in high-concentration indoor air chemicals detected in newly constructed houses (Onuki et al. 2009)

cThe six most abundant substances

dTVOC as the toluene equivalent of substances with carbon lengths from C6 (n-hexane) to C16 (hexadecane)

The statistical significance of the change in IAQ over the month between these samples was determined via the Wilcoxon signed-rank test. The median values of the top six substances decreased significantly, except for ethyl acetate.

In the living room and bedroom, airborne chemical concentrations were significantly lower 1 month after the construction than at 1 week after construction (Fig. 2).
Fig. 2

a Changes in 2-butanone concentration over time, b changes in butyl acetate over time, c changes in ethyl acetate concentration over time, d changes in acetone concentration over time, e changes in ethanol concentration over time, f changes in undecane concentration over time, and g changes in TVOC concentration over time

All five targeted substances concentrations were below the guideline values both 1 week after construction and 1 month after construction. Furthermore, those concentrations were less than half the guideline values specified by the national act.

The concentrations of standardized substances in the houses tested by us were found to be lower than those data from IAQ-S 2009.

All concentrations were lower than the guideline values by about 0.67 to 0.1 times. The difference in the maximum values was even larger, with the values lower by about 0.25 to 0.003 times. In the houses tested by us, the concentrations of all substances were sufficiently lower than the guideline values. The median values of the top six substances were almost equal. The maximum values in this study were about 0.43 to 0.03 times lower than the maximum values recorded in the study IAQ-S 2009. As for TVOC, the median value in this study was about 0.33 times lower and the maximum value about 0.05 times lower than the data from 2009. Since the measurements were completed within 6 months after the completion of construction in IAQ-S 2009, it was emphasized that the IAQ-S 2015 houses had much better IAQ than those tested in 2009.

At the second sampling, the temperature was higher by 2.0–2.7 °C at the median value than the first time. Among the reported environmental parameters, temperature influences the VOC emissions from building materials (Bremer et al. 1993; Wolkoff 1998; Yang 1999); therefore, these differences in the temperature likely had some effects on the concentrations of VOCs in the second samples; a slight increase in temperature led to a significant decrease in chemical concentrations in the second samples even with this effect. The results indicate that the concentrations were at healthy levels according to the guideline values by the national act even 1 week after construction ended, and that the risk of chemical exposure was greatly reduced after 1 month. From this result, it may be preferable to move to new houses 1 month after the construction.

The emission rates of interior and building materials chosen in this study are shown in Table 5. These materials were examined by the chamber test. All five substances mentioned in the national act were present in very low concentrations, and estimating those emission sources was difficult. Regarding the six most abundant substances, as the interior materials used in the floors, walls, and ceilings are considered to have almost the same contribution rate, the emission source was estimated from the results of the emission rate test. The contribution rates of the sash windows, substrate panels, and doors are low considering the area used, but large amounts of adhesive and sealing agents are utilized in those materials, and it is assumed that solvent chemicals such as 2-butanone and acetone are emitted from them. Acetone also originates from the flooring (solid wood), and ethanol primarily originates from the floorboards (painted finish and solid wood), sash windows, and doors. Ethyl acetate is provided by the flooring (sheet finish and solid wood) and substrate panels. Flooring and substrate panels are also assumed to be the main sources of butyl acetate. The emission of undecane was not detected in the preliminary chamber tests conducted; however, a previous study found its volatilization from floor adhesives, floor waxes, and wood stains (Sarigiannis et al. 2011). More research is needed regarding the sources of this compound. All five substances mentioned in the national act were at low concentrations. It was difficult to estimate the emission source.
Table 5

Small-chamber tests of building materials used in the study houses

Building materials

Emission rate (µg/m2/h)

Selected

Formaldehyde

Toluene

Xylene

Styrene

Ethylbenzene

2-Butanone

Acetone

Ethanol

Ethyl acetate

Butyl acetate

Undecane

TVOC

Floorboards (painted finish)

7

NDa

ND

ND

1

ND

7

24

2

5

ND

138

b

4

ND

ND

ND

1

ND

6

19

2

4

ND

130

10

ND

ND

ND

ND

ND

7

23

1

11

ND

96

5

ND

6

ND

5

ND

32

1

6

ND

ND

234

ND

ND

ND

ND

ND

ND

ND

ND

ND

ND

ND

910

ND

ND

ND

ND

ND

ND

5

2

1

1

ND

663

ND

ND

4

ND

4

ND

7

2

4

16

ND

802

Flooring (sheet finish)

ND

ND

ND

ND

ND

ND

ND

ND

ND

38

ND

147

4

ND

ND

ND

ND

9

ND

ND

ND

41

ND

99

1

1

ND

ND

ND

1

ND

ND

ND

28

ND

183

1

ND

ND

ND

ND

ND

ND

ND

ND

222

ND

688

2

ND

ND

ND

ND

6

ND

ND

ND

13

ND

402

ND

ND

ND

ND

ND

ND

ND

ND

ND

27

ND

432

Flooring (solid wood)

3

1

ND

ND

ND

ND

36

2

ND

3

ND

19

2

1

ND

ND

ND

ND

21

44

6

29

ND

138

2

1

4

ND

ND

ND

178

2

ND

4

ND

246

5

9

16

ND

6

2

166

13

ND

5

ND

277

6

18

12

ND

11

3

328

13

4

8

ND

492

4

13

ND

ND

ND

ND

28

ND

8

1

ND

538

7

4

ND

ND

ND

ND

44

1

1

2

ND

2190

Wallpaper

2

3

ND

ND

ND

ND

ND

ND

ND

ND

ND

26

1

7

ND

ND

ND

ND

ND

ND

ND

ND

ND

130

2

ND

ND

ND

ND

ND

ND

ND

ND

ND

ND

145

2

ND

ND

ND

ND

ND

ND

ND

ND

ND

ND

11

Window sash and door

ND

1

5

10

ND

65

18

17

116

3

ND

288

ND

ND

5

12

ND

61

16

29

107

2

ND

222

ND

ND

4

11

ND

54

16

36

93

2

ND

220

ND

5

ND

ND

ND

381

18

8

392

12

ND

504

Substrate panel

5

ND

ND

ND

ND

ND

11

5

1

47

ND

215

ND

ND

ND

ND

ND

ND

10

ND

ND

31

ND

143

ND

ND

ND

ND

ND

ND

2

4

2

45

ND

95

4

ND

ND

ND

ND

ND

11

3

ND

13

ND

45

27

3

2

ND

ND

ND

ND

ND

ND

ND

ND

1727

3

ND

ND

ND

ND

ND

ND

ND

ND

ND

ND

2727

aND: Not detected

bBuilding materials selected this study

With this preliminarily data about the low-VOC building materials, builders will be able to build healthier houses. In Europe, a list of substances and associated emission limits, EU-LCI values, have been developed and were issued in (European Collaborative Action 2013). In Japan, on the other hand, a labeling system for building materials is only prescribed for formaldehyde. Development of such improved labeling on building materials is expected also in Japan to protect the people’s health.

Furthermore, in the houses examined by us, the six most abundant substances have no guideline values in Japan’s national standards. Although the health risks due to these compounds have not been clarified, unregulated substances have often been used as substitutes for regulated solvents. In recent years, some reports have indicated their adverse health impacts on humans (Yu and Crump 1998; Ravindra et al. 2001; Kamijima et al. 2002; Tuomainen et al. 2004; Gallego-Iniesta García et al. 2010). Thus, to prevent diseases and symptoms which are caused by indoor air pollutants, the concentrations of these unregulated substances should still be reduced and minimized.

Conclusion

The reduction in the concentration levels of the five substances, which are regulated by national act, six most abundant substances, and TVOC in the newly built houses over 1 month, was confirmed. The results in this study suggest that the concentrations would possibly be low enough even 1 week after construction ended, and that the concentrations of chemical substances reduced even further after a month if the building materials are carefully chosen.

The research group is constantly updating a database of low-VOC building materials (Suzuki et al. 2018). By choosing low-VOC building materials in advance, houses with low concentrations of volatile chemicals can be constructed.

As a next step of the research, measuring the indoor air chemicals with furniture will be planned. The airborne chemical substances in a room often are estimated to arise from furniture and other home goods. Additionally, investigating the intervention of the efficiency of ventilation systems will be planned.

Notes

Acknowledgement

This study was supported by Sekisui House Ltd and JSPS (Japan Society for the Promotion of Science) Grants-in-Aid for Scientific Research (C) Grant Number 18K13885.

References

  1. Azuma K, Uchiyama I, Uchiyama S et al (2016) Assessment of inhalation exposure to indoor air pollutants: screening for health risks of multiple pollutants in Japanese dwellings. Environ Res 145:39–49CrossRefGoogle Scholar
  2. Begerow J, Jermann E, Keles T et al (1995) Passive sampling for volatile organic compounds (VOCs) in air at environmentally relevant concentration levels. Fresenius J Anal Chem 351(6):549–554CrossRefGoogle Scholar
  3. Bornehag C-G, Stridh G (2000) Volatile organic compounds (VOC) in the Swedish housing stock. Proc Healthy Build 1:437–442Google Scholar
  4. Bremer J, Witte E, Schneider D (1993) Measurement and characterisation of emissions from PVC materials for indoor use. In: Proceedings of the sixth international conference on indoor air quality and climate, Helsinki, FinlandGoogle Scholar
  5. Cox SS, Little JC, Hodgson AT (2002) Predicting the emission rate of volatile organic compounds from vinyl flooring. Environ Sci Technol 36(4):709–714CrossRefGoogle Scholar
  6. European Collaborative Action (2013) Urban air, indoor environment and human exposure, environment and quality of life, report no 29. http://publications.jrc.ec.europa.eu/repository/bitstream/JRC83683/eca%20report%2029_final.pdf
  7. Finland’s Ministry of the Environment (2002) The national building code of Finland. D2-indoor climate and ventilation, regulations and guidelines 2003, Helsinki. http://www.environment.fi. Accessed 18 Feb 2019
  8. Gallego-Iniesta García MP, Moreno Sanroma A, Martín Porrero MP et al (2010) Reactivity of 2-ethyl-1-hexanol in the atmosphere. Phys Chem Chem Phys PCCP 12(13):3294–3300CrossRefGoogle Scholar
  9. Heinrich J (2011) Influence of indoor factors in dwellings on the development of childhood asthma. Int J Hyg Environ Health 214(1):1–25CrossRefGoogle Scholar
  10. Herberth G, Gubelt R, Röder S et al (2009) Increase of inflammatory markers after indoor renovation activities: the LISA birth cohort study. Pediatr Allergy Immunol 20(6):563–570CrossRefGoogle Scholar
  11. Holøs S, Yang A, Lind M et al (2019) VOC emission rates in newly built and renovated buildings, and the influence of ventilation—a review and meta-analysis. Int J Vent 18(3):153–166CrossRefGoogle Scholar
  12. Japanese Ministry of Health Lab and Welf (1997) The 22nd committee on sick house syndrome. Indoor air pollution. https://www.mhlw.go.jp/english/index.html. Accessed 18 Feb 2019
  13. Järnström H, Saarela K, Kalliokoski P et al (2006) Reference values for indoor air pollutant concentrations in new, residential buildings in Finland. Atmos Environ 40(37):7178–7191CrossRefGoogle Scholar
  14. Kamijima M, Sakai K, Shibata E et al (2002) 2-Ethyl-1-hexanol in indoor air as a possible cause of sick building symptoms. J Occup Health 44(3):186–191CrossRefGoogle Scholar
  15. Katsoyiannis A, Leva P, Kotzias D (2008) VOC and carbonyl emissions from carpets: a comparative study using four types of environmental chambers. J Hazard Mater 152(2):669–676CrossRefGoogle Scholar
  16. Klepeis NE, Nelson WC, Ott WR et al (2001) The national human activity pattern survey (NHAPS): a resource for assessing exposure to environmental pollutants. J Expo Anal Environ Epidemiol 11(3):231–252CrossRefGoogle Scholar
  17. Ministry of Health, Labour and Welfare of Japan (2000) The standard methods of air sampling and measurement. https://www.mhlw.go.jp/www1/houdou/1206/h0629-2_b_13.html. Accessed 18 Feb 2019 (in Japanese)
  18. Ministry of Land, Infrastructure, Transport and Tourism and JIS (2015) A 1961. Indoor air-General aspects of sampling strategy. Indoor air-Sampling strategy for formaldehyde. http://kikakurui.com/a1/A1960-2015-01.html. Accessed 18 Feb 2019 (in Japanese)
  19. Ministry of Transport Building and Housing of Denmark (2018) Executive order on building regulations 2018 (BR18). http://bygningsreglementet.dk/~/media/Br/BR-English/BR18_Executive_order_on_building_regulations_2018.pdf. Accessed 18 Feb 2019
  20. Mølhave L (2003) Organic compounds as indicators of air pollution. Indoor Air 13:12–19CrossRefGoogle Scholar
  21. Mori C, Todaka E (2011) A new concept for protecting our children in Environmental contaminants and children’s health. Maruzen Planet Co. Ltd, Tokyo, pp 99–115Google Scholar
  22. Noguchi M, Mizukoshi A, Yanagisawa Y et al (2016) Measurements of volatile organic compounds in a newly built daycare center. Int J Environ Res Public Health 13:736.  https://doi.org/10.3390/ijerph13070736 CrossRefGoogle Scholar
  23. Norbäck D, Björnsson E, Janson C et al (1995) Asthmatic symptoms and volatile organic compounds, formaldehyde, and carbon dioxide in dwellings. Occup Environ Med 52(6):388–395CrossRefGoogle Scholar
  24. Norbäck D, Wieslander G, Nordström K et al (2000) Asthma symptoms in relation to measured building dampness in upper concrete floor construction, and 2-ethyl-1-hexanol in indoor air. Int J Tuber Lung Dis 4(11):1016–1025Google Scholar
  25. Onuki A, Saitou I, Takahiro T et al (2009) Trends in indoor air chemicals detected at high concentrations in newly built houses. Ann Rep Tokyo Metr Inst Pub Health 60:245–251Google Scholar
  26. Ravindra K, Mittal AK, Van Grieken R (2001) Health risk assessment of urban suspended particulate matter with special reference to polycyclic aromatic hydrocarbons: a review. Rev Environ Health 16:169–189CrossRefGoogle Scholar
  27. Raw GJ, Coward SKD, Brown VM et al (2004) Exposure to air pollutants in English homes. J Expo Sci Environ Epidemiol 14(S1):S85–S94CrossRefGoogle Scholar
  28. Rehwagen M, Schlink U, Herbarth O (2003) Seasonal cycle of VOCs in apartments. Indoor Air 13(3):283–291CrossRefGoogle Scholar
  29. Sarigiannis DA, Karakitsios SP, Gotti A et al (2011) Exposure to major volatile organic compounds and carbonyls in European indoor environments and associated health risk. Environ Int 37(4):743–765CrossRefGoogle Scholar
  30. Scholz H, Santl H (1999) Occurrence and assessment of selected volatile organic compounds (VOC) in indoor air. Proc Indoor Air 1:481–486Google Scholar
  31. Seife C (1999) Headache in orbit. New Sci 163(2197):1–5Google Scholar
  32. Seifert B (1992) Regulating indoor air. In: Knöppel H, Wolkoff P (eds) Chemical, microbiological, health and comfort aspects of indoor air quality—state of the art in SBS. Eurocourses: chemical and environmental science, vol 4. Springer, DordrechtGoogle Scholar
  33. Shields HC, Fleischer DM, Weschler CJ (1996) Comparisons among VOCs measured in three types of US commercial buildings with different occupant densities. Indoor Air 6(1):2–17CrossRefGoogle Scholar
  34. Suzuki N, Nakaoka H, Hanazato M et al. (2018) Emission rates of substances from low-volatile-organic-compound paints. Int J Environ Sci Technol 1–8Google Scholar
  35. The Swedish National Board of Housing, Building and Planning and Boverket (2002) Boverkets byggregler 2002, 19, Sweden. http://www.boverket.se
  36. Tuomainen M, Pasanen A-L, Tuomainen A et al (2001) Usefulness of the finnish classification of indoor climate, construction and finishing materials: comparison of indoor climate between two new blocks of flats in Finland. Atmos Environ 35:305–313CrossRefGoogle Scholar
  37. Tuomainen A, Seuri M, Sieppi A (2004) Indoor air quality and health problems associated with damp floor coverings. Int Arch Occup Environ Health 77(3):222–226CrossRefGoogle Scholar
  38. Wieslander G, Norbäck D, Edling C (1997) Airway symptoms among house painters in relation to exposure to volatile organic compounds (VOCs)—a longitudinal study. Ann Occup Hyg 41(2):155–166CrossRefGoogle Scholar
  39. Wolkoff P (1998) Impact of air velocity, temperature, humidity, and air on long-term VOC emissions from building products. Atmos Environ 32(14–15):2659–2668CrossRefGoogle Scholar
  40. Wolkoff P (1999) How to measure and evaluate volatile organic compound emissions from building products. A perspective. Sci Total Environ 227(2–3):197–213CrossRefGoogle Scholar
  41. Wolkoff P, Nielsen GD (2001) Organic compounds in indoor air—their relevance for perceived indoor air quality? Atmos Environ 35(26):4407–4417CrossRefGoogle Scholar
  42. Wolkoff P, Schneider T, Kildesø J et al (1998) Risk in cleaning: chemical and physical exposure. Sci Total Environ 215(1–2):135–156CrossRefGoogle Scholar
  43. Yang X (1999). Study of building material emissions and indoor air quality (Doctoral dissertation, Massachusetts Institute of Technology). https://dspace.mit.edu/handle/1721.1/9366#files-area
  44. Yu C, Crump D (1998) A review of the emission of VOCs from polymeric materials used in buildings. Build Environ 33(6):357–374CrossRefGoogle Scholar

Copyright information

© The Author(s) 2019

Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.