Advertisement

Building Simulation

, Volume 9, Issue 2, pp 141–151 | Cite as

Modelling and multi-scenario analysis for electric heat tracing system combined with low temperature district heating for domestic hot water supply

  • Xiaochen YangEmail author
  • Hongwei Li
  • Svend Svendsen
Research Article Building Systems and Components

Abstract

Low temperature district heating (LTDH) is a cost-efficient way of supplying space heating and domestic hot water (DHW) for buildings in urban areas. However, there is concern that the potential hygiene problems (Legionella) might occur if LTDH is implemented, especially for large buildings. In this study, electric heat tracing system was investigated as a solution to this dilemma. A model of electric heat tracing system for multi-storey buildings was built. Various pipe materials and insulation thicknesses as the parameters of the model were compared to make a comprehensive study. The performance of the electric heating tracing system with LTDH was simulated by taking the user pattern into account. A smart control method based on thermostatic and real-time control was developed, and compared with normal control method. The impact of user pattern was tested by applying standard, stochastic, and real load profiles to the model. The energy and economy performances of electric heat tracing system in different scenarios were simulated by Matlab. The results were compared to the conventional circulation system with the current generation district heating. The electric heat tracing system with LTDH showed good performance on heat loss saving, and it also gave benefits to district heating network by sharing part of the heating load.

Keywords

low temperature district heating domestic hot water electric heat tracing user pattern profile smart control modelling Legionella prevention 

Preview

Unable to display preview. Download preview PDF.

Unable to display preview. Download preview PDF.

References

  1. Bøhm B (2013). Production and distribution of domestic hot water in selected Danish apartment buildings and institutions. Analysis of consumption, energy efficiency and the significance for energy design requirements of buildings. Energy Conversion and Management, 67: 152–159.CrossRefGoogle Scholar
  2. BR10 (2010). Danish Building Regulations. Copenhagen: The Danish Ministry of Economic and Business Affairs & Danish Enterprise and Construction Authority.Google Scholar
  3. Ciesielski CA, Blaser MJ, Wang WLL (1984). Role of stagnation and obstruction of water-flow in isolation of Legionella-pneumophila from hospital plumbing. Applied and Environmental Microbiology, 48: 984–987.Google Scholar
  4. European Commission (2013). Commission Delegated Regulation (EU) of 18.2.2013. Brussels: European Commission.Google Scholar
  5. DS 439 (2009). Code of Practice for Domestic Water Supply Installations. Copenhagen. (in Danish)Google Scholar
  6. DS 452 (2013). Insulation of Thermal Installations. Charlottenlund: Danish Standard. ( in Danish)Google Scholar
  7. DS/CEN/TR16355 (2012). Recommendations for Prevention of Legionella Growth in Installations Inside Buildings Conveying Water for Human Consumption. Copenhagen: European Committee for Standardization.Google Scholar
  8. Dyrelund A (2010). Heat plan Denmark—Low carbon urban heating. Rambø, Danmark: CTR FRB.Google Scholar
  9. EWGLI group (2005). European Guidelines for Control and Prevention of Travel Associated Legionnaires’ Disease. European Commission.Google Scholar
  10. Geberit (2014). Mapress rustfrit systemrør. Available at http://catalog.geberit.com/public/product.aspx?cat=DK_DK-da_1&ch=218&p=63766.Google Scholar
  11. Grontmij (2013). A/S 2600 Golstrup. Available at http://www.grontmij.dk/en/services/energy-climate/district-heating/pages/default.aspx. Accessed 24 Jun 2013.Google Scholar
  12. Lund H, Werner S, Wiltshire R, Svendsen S, Thorsen JE, Hvelplund F, Mathiesen BV (2014). 4th Generation District Heating (4GDH): Integrating smart thermal grids into future sustainable energy systems. Energy, 68: 1–11.CrossRefGoogle Scholar
  13. Olsen KH (2001). Legionellabekæmpelse med varmekabler. VVS BRUGSVAND, 2: 20–22. (in Danish)Google Scholar
  14. Reidhav C, Werner S (2008). Profitability of sparse district heating. Applied Energy, 85: 867–877.CrossRefGoogle Scholar
  15. Rockwool (2014a). Den lille tekniske, En guide til teknisk isolering af rør og installationer. Available at http://www.rockwool-rti.dk/files/RTI/rockwool_den_lille_tekniske.pdf.Google Scholar
  16. Rockwool (2014b) Rørskål 800. Available at http://www.rockwool.dk/produkter/u/8052/vvs-isolering/roerskaal-800.Google Scholar
  17. Uponor (2006). Håndbog for Uponor Brugsvandssystem PEX. Uponor A/S, Glostrup. Available at https://www.uponor.dk/~/media/countryspecific/denmark-bld/download-centre/current/haandbook-vvs/s535-540_up_vvs2010_udgaaede-quickman_lr.pdf?version=1.Google Scholar
  18. van der Kooij D, Veenendaal HR, Scheffer WJH (2005). Biofilm formation and multiplication of Legionella in a model warm water system with pipes of copper, stainless steel and crosslinked polyethylene. Water Research, 39: 2789–2798.CrossRefGoogle Scholar
  19. Viega (2014). Smartloop inliner beregning. Available at http://www.viega.dk/cps/rde/xbcr/dadk/smartloop_inliner_beregning.pdf.Google Scholar

Copyright information

© Tsinghua University Press and Springer-Verlag Berlin Heidelberg 2015

Authors and Affiliations

  1. 1.Civil Engineering DepartmentTechnical University of DenmarkKgs. LyngbyDenmark