1 Introduction

A challenge faced by protection and planning engineers is to study the impact of increased renewable penetration on system protection [1,2,3,4]. The reason is that short-circuit models of conventional generators are not adequately representative of the substantially different, and in some cases complex, fault response of renewables. Power electronics associated with renewable generators produce current waveform signatures that are substantially different and in some cases more complex than those of conventional synchronous or asynchronous generators. To study the impact on protection, it is necessary to use sufficiently accurate models of renewables.

In previous papers, the authors have presented generic electromagnetic transient-type (EMT-type) models of aggregated wind turbine generators (WTGs) or wind parks suitable for transient studies for Type-III (doubly-fed induction generator, DFIG) and Type-IV (full-size converter, FSC) WTGs [5, 6]. These EMT-type models can emulate the time-domain fault response of an actual WTG. Taking these detailed models as references, phasor domain models were developed and an iterative algorithm to integrate these models into protection tools based on steady-state solvers was proposed [7,8,9]. The phasor models reproduce the steady-state short circuit behavior of detailed models.

This paper validates the Type-III generic model and its phasor equivalents using actual fault records of two wind parks consisting of Type-III WTGs and connected to 115 kV and 230 kV transmission systems. The objective is to show qualitatively that the generic model and its phasor equivalent can reproduce the actual fault response in simulations. A simplified phasor model requiring less input is also proposed and validated.

A distinctive characteristic of a WTG is its substantially different negative sequence fault current contribution compared to a synchronous generator [1, 10], and it is necessary for a WTG model to account for the negative sequence behavior. The paper shows that the generic model can reproduce the negative sequence behavior and can be used for fault studies involving negative sequence-based protection.

This paper shows that it is possible to match the actual fault recordings using generic models once the pre-fault conditions are taken into account, and model parameters are properly set considering wind park controller and fault ride through (FRT) schemes. Therefore, it is possible for protection engineers to obtain precise models of their wind generation fleet by tuning generic models using fault records.

2 Generic type-III WTG model

References [5,6,7,8,9] have presented the generic Type-III WTG model used in this paper. This section presents a summary of the main features of the model.

Figure 1 shows a typical configuration for a Type-III WTG. The stator of the DFIG is directly connected to the grid, and the wound rotor is connected to the grid through a back-to-back converter system. The back-to-back converter system consists of two three-phase pulse-width modulated (PWM) converters, one rotor-side converter (RSC) and one grid-side converter (GSC) connected by a DC bus. A line inductor and an AC filter are used at the GSC to improve the power quality. A crowbar is used to protect the RSC against over-currents and the DC capacitors against over-voltages. During crowbar ignition, the RSC is blocked, and the machine behaves like a squirrel cage induction machine (consuming reactive power). Therefore, the DC resistive chopper is widely used to limit the DC voltage and avoid the crowbar ignition during AC faults.

Fig. 1
figure 1

Type-III WTG configuration

The Type-III control is achieved by controlling the RSC and the GSC through vector control techniques. The RSC controls the active and reactive powers delivered to the grid and follows a tracking characteristic to adjust the generator speed for optimal power generation depending on the wind speed. On the other hand, the GSC is used to maintain the DC bus voltage at nominal value and regulate the positive sequence voltage at the medium-voltage side of wind turbine transformer. This objective is commonly achieved through a cascaded control structure consisting of an outer loop which regulates the DC and positive sequence voltage and an inner current loop which regulates the GSC current. The GSC has two control modes: coupled and decoupled sequences. In coupled sequence control mode, the objective is to fully eliminate the negative-sequence current which requires the converter to inject balanced three-phase currents even during unbalanced loading conditions or faults. To achieve this objective, the setpoints of the negative sequence d-axis and q-axis currents are set at zero while the set points of the positive-sequence d-axis and q-axis currents are determined based on the terminal voltage and reference power. The coupled sequence control results in second harmonic power oscillations in GSC power output under unbalanced loading conditions or faults which translates into second harmonic oscillations on the DC voltage and harmonic currents. To eliminate these oscillations, the decoupled sequence control injects a negative sequence current whose amplitude is proportional to the negative sequence terminal voltage. Thus, in contrast to coupled sequence control, under decoupled sequence control the converter must deliver negative-sequence current. For validation studies coupled sequence control mode is selected.

It should be noted that, it is possible to use the GSC to support the grid with reactive power during faults. Further, the same reactive power/AC voltage and power factor control schemes in the GSC control of Type-IV exist in the RSC of Type-III, and in the same way, these control modes are done on positive sequence parameters. For the two converters of one Type-III, the active power flow can be bidirectional. All the settings of the wind parks used for validation studies are provided in the Appendix A.

3 Validation

Two sets of actual relay recordings are available for the fault response of two wind parks consisting of Type-III WTGs and connected to 230 kV and 115 kV North-American transmission systems. Hereinafter in this paper, these two data sets are referred to as Fault 1 (230 kV system) and Fault 2 (115 kV system). The objective is to show that the detailed generic model can reproduce the fault recordings in simulations. The equivalent phasor domain model has been validated by showing that it matches the detailed model in steady state. Simulation tests have been carried on a model of the actual system including WTGs developed in EMTP [11].

3.1 Fault 1

Fault 1 is a fault in a 230 kV transmission system close to a wind park. Figure 2 shows the system and the wind park which embeds 66×1.5 MW Type-III WTGs connected to a collector substation through three 34.5 kV collector circuits and a Y-Δ-Y type 34.5 kV/230 kV step-up transformer. An 18.7 km tie-line connects the collector substation to a 230 kV point of interconnection (POI) substation. The fault is phase B to phase C occurring on the tie-line 3.5 km from the POI substation. Prior to the fault, all 66 WTGs were connected to the system, the park was delivering 25.69 MW and absorbing 1.35 Mvar from the 230 kV system at the collector substation, and the wind speed was 6.5 m/s. The fault event was recorded by the line relays on the 230 kV tie-line. The current differential relay systems that are applied to this line recorded the currents at both terminals in each relay.

Fig. 2
figure 2

Fault 1 in 230 kV system

A model of the system of Fault 1 has been developed in EMTP. The model represents the wind park by the generic aggregated model [5], the tie-line by a PI section, and the rest of the transmission grid by an ideal-source behind an impedance. The fault has been simulated by connecting phases B and C of the PI section 3.5 km from the POI. The parameters of the actual wind park were not available. Therefore, the parameters of the generic model have been set to achieve maximum consistency between simulation results and fault recordings. Appendix A Table A1 presents the parameters of WTG model.

Figures 3, 4, 5, 6, 7 and 8 compare the actual response of the wind park recorded by the relays (dashed line) against the simulation results (solid line). The results are scaled so that the root-mean-square (RMS) magnitudes of the waveforms are displayed as peak values. The fault occurs 3.8 cycles into the simulation and is cleared within 3 cycles. The dashed line waveforms are recorded by the POI substation relay; they are sampled and processed by the wind park collector substation relay and transmitted to the POI substation relay. The tie-line is protected by a digital line current differential relay system, so the currents from both relays are recorded in either relay fault record.

Fig. 3
figure 3

Unfiltered phase currents from wind park measured at collector substation under Fault 1

Fig. 4
figure 4

Filtered phase currents from wind park measured at collector substation under Fault 1

Fig. 5
figure 5

Sequence currents from wind park measured at collector substation under Fault 1

Fig. 6
figure 6

Unfiltered phase voltages on line side of collector substation under Fault 1

Fig. 7
figure 7

Filtered phase voltages on line side of collector substation under Fault 1

Fig. 8
figure 8

Sequence voltages on line side of collector substation under Fault 1

Figure 3 illustrates the unfiltered phase currents from the wind park measured at the collector substation. Fig. 4 presents the filtered phase current (60 Hz) from the wind park measured at the collector substation. Fig. 5 depicts the sequence currents (based on the 60 Hz component) from wind park measured at the collector substation. Fig. 6 shows the unfiltered phase voltages on the line side of the collector substation. Fig. 7 presents the filtered phase voltages (60 Hz) on the line side of the collector substation. Fig. 8 depicts the sequence voltages on the line side of the collector substation. As shown, the simulation results match closely the actual recordings. There are some differences particularly in the first cycle after the fault where high-frequency oscillations observed in simulations do not appear in the recorded data. The reason for this difference is that the sampling rate of the recordings is 16 samples per-cycle which is too low to capture these high-frequency oscillations. By contrast, the simulation sampling rate is 167 samples per cycle in EMTP and hence, the high-frequency oscillations manifest themselves in the simulation. Furthermore, some differences exist in the pre-fault current waveforms as the recorded currents are unbalanced while the simulated currents are balanced. The reason is that these imbalances were not modeled in the EMTP simulation model.

To validate the phasor domain equivalent model, Fault 1 has been simulated in phasor domain using the phasor domain model and the results have been compared to those of the generic EMT-type model. The simulation scenario is the same except that the fault is assumed to be permanent to enable comparison between the EMT-type and phasor domain results. The parameters of the phasor domain equivalent model are based on Appendix A Table A1.

Two versions of the phasor domain model have been tested: a detailed version as outlined in [2, 8, 9] and a new simplified version as proposed in this work. They have two main differences: the first is the method of establishing the dq reference frame of voltage and flux. The simplified model assumes the phase angle difference between the reference angle of voltage and flux dq frame to be always 90° whereas the detailed model represents this phase angle as a variable and calculates it using the parameters in detailed EMT-type model. This difference results in a discrepancy between the calculated d-axis and q-axis quantities of the simplified and detailed models. The second difference is the method of calculation of negative-sequence current. The detailed model accurately reproduces the negative-sequence current of the EMT-type model and requires many inputs, whereas the simplified model estimates the negative sequence current using a simple relation that divides negative sequence voltage by equivalent machine impedance in [12].

Tables 1, 2 and 3 compare the simulation results of the EMT-type model and the phasor domain equivalent model suggesting a satisfactory match between the two models.

Table 1 Positive and negative sequence currents (I1 and I2) and voltages (V1 and V2) at the terminal of GSC under Fault 1
Table 2 Positive and negative sequence currents and voltages at collector under Fault 1
Table 3 Positive and negative sequence currents and voltages (RMS values) at collector under Fault 1

3.2 Fault 2

Fault 2 occurs close to a wind park in a 115 kV transmission system. Figure 9 shows the system which is a portion of a 115 kV transmission system. The wind park embeds 11×1.5 MW Type-III WTGs connected to a 34.5 kV collector circuit. A Y-Δ-Y type 34.5 kV/115 kV step-up transformer connects the collector circuit to a 115 kV POI/collector substation. A 10.7 km tie-line connects the POI/collector substation to a network substation. The fault was a phase A to ground occurring on the line to the network substation, 3.8 km from the network substation. Prior to the fault, all 11 WTGs were connected to the system, and the plant was supplying 17.7 MW and 3.2 Mvar into the grid.

Fig. 9
figure 9

Fault 2 in 115 kV system

A model of the system of Fault 2 has been developed in EMTP. The model represents the wind park by the generic model [5], the tie-line by a PI section, and the rest of the transmission grid by an ideal-source behind an impedance. The fault has been simulated by connecting phase A of the PI section to the ground. Table 7 presents the parameters of the wind park model.

Figures 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20 and 21 compare the actual response of the wind park recorded by the relays (dashed line) against simulation results (solid line). The results are scaled so that the RMS magnitudes for the waveforms are displayed as peak values. The fault event was recorded by the line relays at the network and the POI/collector substations.

Fig. 10
figure 10

Unfiltered phase voltages at network substation under Fault 2

Fig. 11
figure 11

Filtered phase voltages at network substation under Fault 2

Fig. 12
figure 12

Sequence voltages at network substation under Fault 2

Fig. 13
figure 13

Unfiltered phase currents from network substation under Fault 2

Fig. 14
figure 14

Filtered phase currents from network substation under Fault 2

Fig. 15
figure 15

Sequence currents from network substation under Fault 2

Fig. 16
figure 16

Unfiltered phase voltages at POI/collector substation under Fault 2

Fig. 17
figure 17

Filtered phase voltages at POI/collector substation under Fault 2

Fig. 18
figure 18

Sequence voltages at POI/collector substation under Fault 2

Fig. 19
figure 19

Unfiltered phase currents from POI/collector under Fault 2

Fig. 20
figure 20

Filtered phase currents from POI/collector substation under Fault 2

Fig. 21
figure 21

Sequence currents from POI/collector substation under Fault 2

Figures 10, 11 and 12 show the unfiltered, filtered (60 Hz), and sequence components of phase voltages on the 115 kV bus at the network substation. Figs. 13, 14 and 15 depict the unfiltered, filtered (60 Hz), and sequence components of phase currents from network substation. Figures 16, 17 and 18 illustrate the unfiltered, filtered (60 Hz), and sequence components of phase voltages at the POI/collector substation. Figures 19, 20 and 21 present the unfiltered, filtered (60 Hz), and sequence components of phase currents from the POI/collector substation. As shown, the simulation results match the actual fault records.

Fault 2 has been simulated in phasor domain using the phasor domain equivalent model and the results have been compared to those of the EMT-type model. The simulation scenario is the same except that the fault is assumed to be permanent to enable comparison between the EMT-type and phasor domain results. The parameters of the phasor domain generic model are based on Appendix A Table A1.

Tables 4, 5 and 6 compare the simulation results of the EMT-type model and its phasor domain equivalent model. The results show a satisfactory match between the generic models.

Table 4 Positive and negative sequence currents and voltages at the terminal of GSC under Fault 2
Table 5 Positive and negative sequence currents and voltages at POI/collector under Fault 2
Table 6 Positive and negative sequence currents and voltages (RMS values) at POI/collector under Fault 2

4 Conclusion

This paper is on the validation of a generic aggregated wind park model for fault studies and its phasor domain equivalent model through cross-examination against actual fault records of two wind parks consisting of Type-III WTGs. The generic model is able to reproduce the time-domain response of the actual wind park to a fault. The phasor model provides the steady-state short-circuit response. A simplified phasor model is also proposed, in which less user input is required due to assumptions and simplifications in the model. It proved to be satisfactory within a margin of a few percent compared to the full phasor model.