Abstract
An incident occurred at a Nitric Acid Plant when a failed 18-in. (457 mm)-diameter 304L stainless steel pipe connecting the Converter to the Tail Gas Catalytic Reactor ruptured. The rupture resulted in thrown fragments and some damage to equipment in the vicinity of the pipe. Normally, pipe operating conditions are about 80 psig (0.55 MPa) and 850–900 °F (454–482 °C), and the nominal thickness of the pipe was 0.180-in. (0.46 mm). This article summarizes the discovery of a very unusual condition of intergranular stress corrosion cracking due to sensitization of the low-carbon stainless steel used in manufacture of the pipe. The lessons learned from this failure investigation are vital to those who use stainless steel in Tail Gas systems.
Similar content being viewed by others
References
W.E. Baker, P.A. Cox, P.S. Westine, J.J. Kulesz, R.A. Strehlow, Explosion Hazards and Evaluation (Elsevier, New York, 1983)
API RP 571, Damage Mechanisms Affecting Fixed Equipment in the Refining Industry, 2nd edn (American Petroleum Institute, 2011), pp. 5–49
M.J. Fox, R.D. McCright, An Overview of Low Temperature Sensitization, Lawrence Livermore National Report No. UCRL-15619 (1983)
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Benac, D.J., Cherolis, N. & Hester, M. Unexpected High-Energy Failure of Type 304L Stainless Steel Piping in the Tail Gas System in Nitric Acid Plant Due to Intergranular Stress Corrosion Cracking (IGSCC). J Fail. Anal. and Preven. 17, 217–227 (2017). https://doi.org/10.1007/s11668-017-0252-0
Received:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s11668-017-0252-0