Macroscopic parameters investigation and transfer characteristics assessment of counter flow packed tower liquid desiccant dehumidifier/regenerator

  • Original Article
  • Published:
Heat and Mass Transfer Aims and scope Submit manuscript

Abstract

In this study, a simplified thermal model is developed for coupled heat and mass transfer processes in a packed tower counter flow adiabatic dehumidifier and regenerator. The developed differential energy and mass conservation equations are simplified to first-order linear differential form and solved using the boundary value problem to predict the macroscopic parameters at the outlet of the dehumidifier/regenerator. Total sixty-nine cases provided in the literature are validated using the developed model for adiabatic dehumidifier/regenerator and observed very good agreement with the average absolute deviation of \(\pm\) 1.47%, \(\pm\) 2.94%, \(\pm\) 1.81%, and \(\pm\) 4.77%, \(\pm\) 4.05%, and \(\pm\) 1.80% for macroscopic parameters such as air outlet temperature, liquid desiccant outlet temperature, and air outlet humidity ratio for dehumidifier and regenerator, respectively. Later, a parametric analysis is carried out to assess the sensitivity of the developed model with the variation in four inlet parametric variances such as air inlet temperature, air inlet specific humidity ratio, and L/G (liquid desiccant/air flow rate) ratio, and desiccant inlet temperature. It is found that air inlet specific humidity ratio, L/G ratio, and liquid desiccant inlet temperature each have a significant influence on tower performance. Furthermore, using the developed model a case study is conducted to analyse the macroscopic parameter characteristic distribution along with the height of the dehumidifier and regenerator. The distinct performance evaluation indices such as dimensionless heat and moisture difference ratio, latent heat ratio, and overall energy exchange in dehumidifier/regenerator along with tower height as performance evaluation parameters were introduced and variation with tower height are evaluated.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
Fig. 13

Similar content being viewed by others

Abbreviations

\({A}_{t}\) :

Specific area of the packed tower (m2/m3)

\({C}_{p}\) :

Specific heat (kJ/kg k)

\(H\) :

Height of the packed tower (m)

\(h\) :

Specific enthalpy (kJ/kg)

\({m}_{r}\) :

Moisture removal rate (kg/s)

\(T\) :

Temperature (°C )

\(\psi\) :

Mass flux (kg/s-m2)

\({\varphi }_{c}\) :

Heat transfer coefficient (w/m2 k)

\(\omega\) :

Specific humidity of air (kg/kg of dry air)

\({\omega }_{e}\) :

Equilibrium air specific humidity (kg/kg of dry air)

\({\varphi }_{m}\) :

Mass transfer coefficient (kg/m2 s)

\(\beta\) :

Latent heat of evaporation (kJ/kg k)

\({\varepsilon }_{T}\) :

Thermal effectiveness (%)

\({\varepsilon }_{m}\) :

Moisture effectiveness (%)

\(\zeta\) :

Liquid desiccant concentration (%)

a:

Air

des:

Desiccant

e:

Equilibrium

w,v :

Water vapour

in:

Inlet

out:

Outlet

AAD:

Average absolute deviation (%)

FDM:

Finite difference model

NTU:

Number of transfer unit

AAD:

Average absolute deviation (%)

FDM:

Finite difference model

NTU:

Number of transfer unit

References

  1. Das RS, Jain S (2015) Simulation of potential standalone liquid desiccant cooling cycles. Energy 81:652–661. https://doi.org/10.1016/j.energy.2015.01.009

    Article  Google Scholar 

  2. Xiao F, Ge G, Niu X (2011) Control performance of a dedicated outdoor air system adopting liquid desiccant dehumidification. Appl Energy 88:143–149. https://doi.org/10.1016/j.apenergy.2010.06.019

    Article  Google Scholar 

  3. Ren H, Sun Y, Lin W et al (2020) A review of heat and mass transfer mechanisms of dehumidifiers and regenerators for liquid desiccant cooling systems. Sci Technol Built Environ 26:465–483. https://doi.org/10.1080/23744731.2019.1686888

    Article  Google Scholar 

  4. Wang L, Xiao F, Zhang X, Kumar R (2016) Une étude expérimentale de la performance de déshumidification d’un déshumidificateur à déshydratant liquide à contre-courant. Int J Refrig 70:289–301. https://doi.org/10.1016/j.ijrefrig.2016.06.005

    Article  Google Scholar 

  5. Chung TW, Ghosh TK, Hines AL (1996) Comparison between Random and Structured Packings for Dehumidification of Air by Lithium Chloride Solutions in a Packed Column and Their Heat and Mass Transfer Correlations. Ind Eng Chem Res 35:192–198. https://doi.org/10.1021/ie940652u

    Article  Google Scholar 

  6. Martin V, Goswami DY (1999) Heat and mass transfer in packed bed liquid desiccant regenerators—an experimental investigation. J Sol Energy Eng Trans ASME 121:162–170. https://doi.org/10.1115/1.2888428

    Article  Google Scholar 

  7. Gao WZ, Liu JH, Cheng YP, Zhang XL (2012) Experimental investigation on the heat and mass transfer between air and liquid desiccant in a cross-flow dehumidifier. Renew Energy 37:117–123. https://doi.org/10.1016/j.renene.2011.06.006

    Article  Google Scholar 

  8. Yin Y, Zhang X, Chen Z (2007) Experimental study on dehumidifier and regenerator of liquid desiccant cooling air conditioning system. Build Environ 42:2505–2511. https://doi.org/10.1016/j.buildenv.2006.07.009

    Article  Google Scholar 

  9. Moon CG, Bansal PK, Jain S (2009) New mass transfer performance data of a cross-flow liquid desiccant dehumidification system. Int J Refrig 32:524–533. https://doi.org/10.1016/j.ijrefrig.2008.06.011

    Article  Google Scholar 

  10. Elsarrag E (2006) Dehumidification of air by chemical liquid desiccant in a packed column and its heat and mass transfer effectiveness. HVAC R Res 12:3–16. https://doi.org/10.1080/10789669.2006.10391164

    Article  Google Scholar 

  11. Ou X, Cai W, He X, Zhai D (2018) Experimental investigations on heat and mass transfer performances of a liquid desiccant cooling and dehumidification system. Appl Energy 220:164–175. https://doi.org/10.1016/j.apenergy.2018.03.087

    Article  Google Scholar 

  12. Su W, Li W, Sun B, Zhang X (2019) Experimental study and correlations for heat and mass transfer coefficients in the dehumidifier of a frost-free heat pump system. Int J Heat Mass Transf 131:450–462

    Article  Google Scholar 

  13. Factor HM, Grossman G (1980) A packed bed dehumidifier/regenerator for solar air conditioning with liquid desiccants. Sol Energy 24:541–550. https://doi.org/10.1016/0038-092X(80)90353-9

    Article  Google Scholar 

  14. Elsayed MM, Gari HN, Radhwan AM (1993) Effectiveness of heat and mass transfer in packed beds of liquid desiccant system. Renew Energy 3:661–668. https://doi.org/10.1016/0960-1481(93)90073-P

    Article  Google Scholar 

  15. Oberg V, Goswami DY (1998) Experimental study of the heat and mass transfer in a packed bed liquid desiccant air dehumidifier. J Sol Energy Eng Trans ASME 120:289–297. https://doi.org/10.1115/1.2888133

    Article  Google Scholar 

  16. Goswami DY, Fumo N (2002) Study of an aqueous lithium chloride desiccant system: air dehumidification and desiccant regeneration. Sol Energy 72:351–361

    Article  Google Scholar 

  17. Liu XH, Jiang Y, Qu KY (2007) Heat and mass transfer model of cross flow liquid desiccant air dehumidifier/regenerator. Energy Convers Manag 48:546–554. https://doi.org/10.1016/j.enconman.2006.06.002

    Article  Google Scholar 

  18. Wang Z, Zhang X, Li Z (2017) Investigation on the coupled heat and mass transfer process between extremely high humidity air and liquid desiccant in the counter-flow adiabatic packed tower. Int J Heat Mass Transf 110:898–907. https://doi.org/10.1016/j.ijheatmasstransfer.2017.03.072

    Article  Google Scholar 

  19. Naik BK, Muthukumar P, Sunil Kumar P (2018) A novel finite difference model coupled with recursive algorithm for analyzing heat and mass transfer processes in a cross flow dehumidifier/regenerator. Int J Therm Sci 131:1–13. https://doi.org/10.1016/j.ijthermalsci.2018.05.029

    Article  Google Scholar 

  20. Stevens DI, Braun JE, Klein SA (1989) An effectiveness model of liquid-desiccant system heat/mass exchangers. Sol Energy 42:449–455. https://doi.org/10.1016/0038-092X(89)90045-5

    Article  Google Scholar 

  21. Ren CQ (2008) Corrections to the simple effectiveness-NTU method for counterflow cooling towers and packed bed liquid desiccant-air contact systems. Int J Heat Mass Transf 51:237–245. https://doi.org/10.1016/j.ijheatmasstransfer.2007.04.028

    Article  MATH  Google Scholar 

  22. Langroudi LO, Pahlavanzadeh H, Mousavi SM (2014) Statistical evaluation of a liquid desiccant dehumidification system using RSM and theoretical study based on the effectiveness NTU model. J Ind Eng Chem 20:2975–2983. https://doi.org/10.1016/j.jiec.2013.11.031

    Article  Google Scholar 

  23. Gandhidasan P (2004) A simplified model for air dehumidification with liquid desiccant. Sol Energy 76:409–416. https://doi.org/10.1016/j.solener.2003.10.001

    Article  Google Scholar 

  24. Gandhidasan P (2005) Quick performance prediction of liquid desiccant regeneration in a packed bed. Sol Energy 79:47–55. https://doi.org/10.1016/j.solener.2004.10.002

    Article  Google Scholar 

  25. Chen XY, Li Z, Jiang Y, Qu KY (2006) Analytical solution of adiabatic heat and mass transfer process in packed-type liquid desiccant equipment and its application. Sol Energy 80:1509–1516. https://doi.org/10.1016/j.solener.2005.12.002

    Article  Google Scholar 

  26. Liu XH, Qu KY, Jiang Y (2006) Empirical correlations to predict the performance of the dehumidifier using liquid desiccant in heat and mass transfer. Renew Energy 31:1627–1639. https://doi.org/10.1016/j.renene.2005.08.029

    Article  Google Scholar 

  27. Babakhani D, Soleymani M (2009) An analytical solution for air dehumidification by liquid desiccant in a packed column. Int Commun Heat Mass Transf 36:969–977. https://doi.org/10.1016/j.icheatmasstransfer.2009.06.002

    Article  Google Scholar 

  28. Babakhani D, Soleymani M (2010) Simplified analysis of heat and mass transfer model in liquid desiccant regeneration process. J Taiwan Inst Chem Eng 41:259–267. https://doi.org/10.1016/j.jtice.2009.10.006

    Article  Google Scholar 

  29. Kiran Naik B, Muthukumar P, Bhattacharyya C (2019) Thermal modelling and parametric investigations on coupled heat and mass transfer processes occurred in a packed tower. Heat Mass Transf 55:627–644. https://doi.org/10.1007/s00231-018-2440-1

    Article  Google Scholar 

  30. Treybal RE (1969) Mass-Transfer Operation, 3rd edn. McGraw-Hill, New York

    Google Scholar 

  31. Oyieke AAY, Inambao FL (2021) A review of coupled heat and mass transfer in adiabatic liquid desiccant dehumidification and regeneration systems; Advances and opportunities. Int J Low-Carbon Technol 16:1–20. https://doi.org/10.1093/ijlct/ctaa031

    Article  Google Scholar 

  32. Luo Y, Yang H, Lu L, Qi R (2014) A review of the mathematical models for predicting the heat and mass transfer process in the liquid desiccant dehumidifier. Renew Sustain Energy Rev 31:587–599

    Article  Google Scholar 

  33. Naik BK, Soni A, Kumar A et al (2016) Coupled Heat and Mass Transfer Analysis of an Adiabatic Dehumidifier - Unique Approach. In: Energy Procedia. Elsevier Ltd, pp 305–315

  34. Conde MR (2004) Properties of aqueous solutions of lithium and calcium chlorides: Formulations for use in air conditioning equipment design. Int J Therm Sci 43:367–382. https://doi.org/10.1016/j.ijthermalsci.2003.09.003

    Article  Google Scholar 

  35. Koronaki IP, Christodoulaki RI, Papaefthimiou VD, Rogdakis ED (2013) Thermodynamic analysis of a counter flow adiabatic dehumidifier with different liquid desiccant materials. Appl Therm Eng 50:361–373

    Article  Google Scholar 

  36. Naik BK, Muthukumar P (2019) Experimental investigation and parametric studies on structured packing chamber based liquid desiccant dehumidification and regeneration systems. Build Environ 149:330–348. https://doi.org/10.1016/j.buildenv.2018.12.028

    Article  Google Scholar 

  37. Aadhithiyan AK, Sreeraj R, Kiran Naik B, Anbarasu S (2021) Assessment of evaporative cooling process across the mechanically driven cooling tower based on two-point boundary value problem using novel integral technique. Int J Refrig 131:254–262. https://doi.org/10.1016/j.ijrefrig.2021.08.002

    Article  Google Scholar 

Download references

Acknowledgements

The author would like to thank AICTE, Delhi, India, for National Doctoral Fellowship Scheme.

Funding

This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-profit sectors.

Author information

Authors and Affiliations

Authors

Contributions

N. S. Deshmukh: Conceptualization, Data curation, Formal analysis, Investigation, Writing-original draft, Software, Validation, B. S. Gawali: Resources, Visualization, Writing—review & editing, Supervision. B. K. Naik: Resources, Visualization, Writing—review & editing. Mahmadrafik S. Choudhari: Data curation, Methodology, Rustum S. Dhalait: Methodology, Project administration.

Corresponding author

Correspondence to Nandkishor S. Deshmukh.

Ethics declarations

Conflict of interest

There is no conflict of interest declared by the authors.

Additional information

Publisher's Note

Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Rights and permissions

Springer Nature or its licensor (e.g. a society or other partner) holds exclusive rights to this article under a publishing agreement with the author(s) or other rightsholder(s); author self-archiving of the accepted manuscript version of this article is solely governed by the terms of such publishing agreement and applicable law.

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Deshmukh, N.S., Gawali, B.S., Naik, B.K. et al. Macroscopic parameters investigation and transfer characteristics assessment of counter flow packed tower liquid desiccant dehumidifier/regenerator. Heat Mass Transfer 59, 1185–1207 (2023). https://doi.org/10.1007/s00231-022-03325-9

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s00231-022-03325-9

Navigation