Abstract
Direct Expansion Variable Refrigerant Flow Air-Conditioning (DX-VRF-A/C) units can be seen in buildings of all sizes. The evaporator in a DX-VRF-A/C unit (or DX air cooling coil), normally generates heat and mass transfer in the form of cooling and dehumidifying of hot and humid air flowing through the cooling coil. DX air-conditioning unit with single speed compressors and forced draft fans usually rely on switch control to maintain only the indoor dry bulb temperature which results in an uncontrolled balance of indoor humidity and reduces thermal comfort, and consequently causes poor indoor air quality (IAQ) as well as produces low energy efficiency. Thus, DX air-conditioning unit with variable-speed compressors and forced draft fans are increasingly adopted in pursuit of higher energy efficiency and thermal comfort indoor environment. Hence, study the simultaneous heat and mass transfer performance in DX air cooling coil of DX air-conditioning unit with variable-speed compressor and forced draft fan is essential, however, research work is still lacking in regards to this A/C system. A comprehensive analysis of the airside cooling and dehumidification process in DX cooling coil and its application are illustrated in this chapter. It commences with introducing the calculation of an important dimensionless parameter, namely steady state Equipment Sensible Heat Ratio (SHR) of DX air cooling coil, which is defined as the ratio of the output sensible cooling capacity of DX cooling coil to the total output cooling capacity. An experimental study on estimating on the dehumidification effect on the airside of the superheated region (SPR) in a DX cooling coil is given. The development of the modified Logarithmic Mean Enthalpy Difference (LMED) method for evaluating the total heat transfer rate in a wet air cooling coil operating under both unit and non-unit Lewis Factors (Le2/3) conditions is reported at the end of this chapter.
Access this chapter
Tax calculation will be finalised at checkout
Purchases are for personal use only
References
Edward GP (1989) Air conditioning principles and systems: an energy approach, second edn.
Lam JC (1996) An analysis of residential sector energy use in Hong Kong. Energy 21(1):1–8
Lam JC (2000) Residential sector air conditioning loads and electricity use in Hong Kong. Energy Convers Manage 41:1757–1768
Brandemuehl MJ, Katejanekarn T (2004) Dehumidification characteristics of commercial building applications. ASHRAE Trans 114(2):65–76
Fanger PO (2001) Human requirements in future air-conditioned environments. Int J Refrig 24(2):148–153
Arens EA, Baughman AV (1996) Indoor humidity and human health: part II-buildings and their systems. ASHRAE Trans 102(1):212–221
Toftum J, Fanger PO (1999) Air humidity requirements for human comfort. ASHRAE Trans 105(2):641–647
Sterling EM, Arundel A, Sterling TD (1985) Criteria for human exposure to humidity in occupied buildings. ASHRAE Trans 91(1B):611–622
Green GH (1982) The positive and negative effects of building humidification. ASHRAE Trans 88(1):1049–1061
ASHRAE (2001) Handbook of fundamentals
Tanabe S, Kimura K, Hara T (1987) Thermal comfort requirements during the summer season in Japan. ASHRAE Trans 93(Pt. 1):564–577
Fountain ME, Arens E, Xu TF, Bauman FS, Oguru M (1999) An investigation of thermal comfort at high humidities. ASHRAE Trans 105(2):94–103
Olesen BW, Brager GS (2004) A better way to predict comfort. ASHRAE J 46(8):20–28
ASHRAE (2001) ANSI/ASHRAE standard 62–2001, ventilation for acceptable indoor air quality
ASHRAE (2000) Handbook-HVAC systems and equipment
Krakow KI, Lin S, Zeng ZS (1995) Temperature and humidity control during cooling and dehumidifying by compressor and evaporator fan speed variation. ASHRAE Trans 101(1):292–304
Andrade MA, Bullard CW, Hancock S, Lubliner M (2002) Modulating blower and compressor capacities for efficient comfort control. ASHRAE Trans 108(1):631–637
Li Z, Deng SM (2007) An experimental study on the inherent operational characteristics of a direct expansion (DX) air conditioning (A/C) unit. Build Environ 42(1):1–10
Li Z, Deng SM (2007) A DDC-based capacity controller of a direct expansion (DX) air conditioning (A/C) unit for simultaneous indoor air temperature and humidity control Part I: Control algorithms and preliminary controllability tests. Int J Refrig 30:113–123
Li Z, Deng SM (2007) A DDC-based capacity controller of a direct expansion (DX) air conditioning (A/C) unit for simultaneous indoor air temperature and humidity control Part II: Further development of the controller to improve control sensitivity. Int J Refrig 30:124–133
Threlkeld JL (1970) Thermal environmental engineering
ASHRAE (2005) ASHRAE fundamentals, mass transfer
Elmahdy AH, Mitalas GP (1977) A simple model for cooling and dehumidifying coils for use in calculating energy requirements for buildings. ASHRAE Trans 83(2):103–117
Jacobi AM, Goldschmidt VW (1990) Low Reynolds number heat and mass transfer measurements of an overall counter-flow baffled finned-tube condensing heat exchanger. J Heat Transfer 33(4):755–765
Jin GY, Cai WJ, Wang YW, Yao Y (2006) A simple dynamic model of cooling coil unit. Energy Convers Manage 47(15–16):2659–2672
McQuiston FC, Parker JD (1994) Heating ventilating and air conditioning, fourth edn.
McQuiston FC (1978) Heat, mass and momentum transfer data for five plate-fin-tube heat transfer surfaces. ASHRAE Trans 84(1):266–293
Theerakulpisut S, Priprem S (1998) Modeling cooling coils. Int Commun Heat Mass Transfer 25(1):127–137
Wang J, Hihara E (2003) Prediction of air coil performance under partially wet and totally wet cooling conditions using equivalent dry-bulb temperature method. Int J Refrig 26(3):293–301
Huzzayyin AS, Nada SA, Elattar HF (2007) Air-side performance of wavy-finned-tube direct expansion cooling and dehumidifying air coil. Int J Refrig 30(2):230–244
Xia Y, Jacobi AM (2005) Air-side data interpretation and performance analysis for heat exchangers with simultaneous heat and mass transfer: wet and frosted surfaces. Int J Heat Mass Transf 48(25–26):5089–5102
Byun JS, Lee JH, Choi JY (2007) Numerical analysis of evaporation performance in a finned-tube heat exchanger. Int J Refrig 30(5):812–820
Hill JM, Jeter SM (1991) A linear subgrid cooling and dehumidification coil model with emphasis on mass transfer. ASHRAE Trans 97(2):118–128
Jia X, Tso CP, Jolly P, Chia PK (1995) A distributed model for prediction of the transient response of an evaporator. Int J Refrig 18(5):336–342
Jia X, Tso CP, Jolly P, Wong YW (1999) Distributed steady and dynamic modeling of dry-expansion evaporators. Int J Refrig 22(2):126–136
Kabelac S (1989) The transient response relations for a serpentine cross-flow heat exchanger with water velocity disturbance. Int J Heat Mass Transf 32(6):1183–1189
Liang SY, Wong TN, Nathan GK (2001) Numerical and experimental studies of refrigerant circuitry of evaporator coils. Int J Refrig 24(8):823–833
Mirth DR, Ramadhyani S (1993) Prediction of cooling-coil performance under condensing conditions. Int J Heat Fluid Flow 14(4):391–400
Myers GE, Mitchell JW, Linderman CF (1970) The transient response of heat exchanger having an infinite capacitance rate fluid. ASME J Heat Transfer 92(2) Series C:269–275
Ramachandran PV (1984) Simulation and optimization of cooling coils. PhD thesis, Department of Mechanical Engineering, Indian Institute of Technology
Vardhan A, Dhar PL (1998) A new procedure for performance prediction of air conditioning coils. Int J Refrig 21(1):77–83
Yu X, Jin W, Smith TF (2005) A model for the dynamic response of a cooling coil. Energy Build 37(12):1278–1289
Xia Y, Jacobi AM (2004) An exact solution to steady heat conduction in a two-dimensional slab on a one-dimensional fin: application to frosted heat exchangers. Int J Heat Mass Transf 47(14–16):3317–3326
Bandyopadhyay G, Gosnold W, Mann M (2008) Analytical and semi-analytical solutions for short-time transient response of ground heat exchangers. Energy Build 40(10):1816–1824
Bielski S, Malinowski L (2005) An analytical method for determining transient temperature field in a parallel-flow three-fluid heat exchanger. Int Commun Heat Mass Transfer 32(8):1034–1044
Kabashnikov VP, Danilevskii LN, Nekrasov VP, Vityaz IP (2002) Analytical and numerical investigation of the characteristics of a soil heat exchanger for ventilation systems. Int J Heat Mass Transf 45(11):2407–2418
Klein H, Eigenberger G (2001) Approximate solutions for metallic regenerative heat exchangers. Int J Heat Mass Transf 44(18):3553–3563
Ren C, Yang H (2006) An analytical model for the heat and mass transfer processes in indirect evaporative cooling with parallel/counter flow configurations. Int J Heat Mass Transf 49(3–4):617–627
Amrane K, Hourahan GC, Potts G (2003) Latent performance of unitary equipment. ASHRAE J 45(1):28–31
Wang G, Liu MS, Claridge DE (2007) Decoupled modeling of chilled-water cooling coils. ASHRAE Trans 113(1):484–493
ASHRAE (1983) Handbook-HVAC systems and equipment
Stevens RA, Fernandez J, Woolf J (1957) Mean temperature difference in one- two- and three-pass crossflow heat exchangers. Trans ASME 79:287–297
Myers RJ (1967) The effect of dehumidification on the air-side heat transfer coefficient for a finned-tube coil. MS thesis, Department of Civil Engineering, University of Minnesota
Chen W, Deng S (2006) Development of a dynamic model for a DX VAV air conditioning system. Energy Convers Manage 47(18–19):2900–2924
Deng SM (2000) A dynamic mathematical model of a direct expansion (DX) water-cooled air-conditioning plant. Build Environ 35(7):603–613
Gungor KE, Winterton RHS (1987) Simplified general correlation for saturated flow boiling and comparisons of correlations with data. Can J Chem Eng Chem Eng Res Des 65:148–156
Kandlikar SG (1990) A general correlation for saturated two-phase flow boiling heat transfer inside horizontal and vertical tubes. ASME J Heat Transf 112(1):219–228
Shah MM (1982) Chart correlation for saturated boiling heat transfer: equations and further study. ASHRAE Trans 88(1):185–196
Boissieux X, Heikal M, Johns R (2000) Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube, part I: evaporation. Int J Refrig 23(4):269–283
Turaga M, Lin S, Fazio PF (1988) Correlations for heat transfer and pressure drop factors for direct expansion air cooling and dehumidifying coils. ASHRAE Trans 94(2):616–629
Hong TK, Webb RL (1996) Calculation of fin efficiency for wet and dry fins. Int J HVAC&R Res 2(1):27–41
McQuiston FC (1975) Fin efficiency with combined heat and mass transfer. ASHRAE Trans 81(1):350–355
Holman JP (1994) Experimental methods for engineers. McGraw-Hill, New York
Brodrick J, Gilbride T (2002) Focusing on buyers’ needs: DOE’s emerging technology program. Energy Eng 99(6):18–37
Chi J, Didion D (1982) A simulation model of the transient performance of a heat pump. Int J Refrig 5(3):176–184
MacArthur JW (1984) Transient heat pump behavior: a theoretical investigation. Int J Refrig 7(2):123–132
Wang H, Touber S (1991) Distributed and non-steady-state modeling of an air cooler. Int J Refrig 14(2):98–111
Fisher SK, Rice CK (1983) The oak ridge heat pump model: I. A steady-state computer design model for air-to-air heat pumps. ORNL/CON-80/R1, Energy Division, Oak Ridge National Lab
Mullen CE, Bridges BD, Porter KJ, Hahn GW, Bullard CW (1997) Development and validation of a room air-conditioning simulation model. ACRC TR-116
Qi Q, Deng SM (2008) Multivariable control-oriented modeling of a direct expansion (DX) air conditioning (A/C) system. Int J Refrig 31(5):841–849
Dittus FW, Boelter LMK (1930) Heat transfer in automobile radiators of the turbulent type. Univ Calif Publ Eng 2:443–461
Eckels PW, Rabas TJ (1987) Dehumidification: on the correlation of wet and dry transport process in plate finned-tube heat exchangers. ASME J Heat Transfer 109:575–582
Pirompugd W, Wang CC, Wongwises S (2007) Finite circular fin method for heat and mass transfer characteristics for plain-fin-and-tube heat exchangers under fully and partially wet surface conditions. Int J Heat Mass Transf 50(3–4):552–565
Seshimo Y, Ogawa K, Marumoto K, Fujii M (1988) Heat and mass transfer performances on plate fin and tube heat exchangers with dehumidification. Trans JSME 54:716–721
Moffat RJ (1988) Describing the uncertainties in experimental results. Exp Thermal Fluid Sci 1:2681–2691
Wang CC (2008) On the heat and mass transfer analogy of fin-and-tube heat exchanger. Int J Heat Mass Transf 51:2055–2059
Acknowledgements
This research was funded by the Ningbo Natural Science Foundation Project, Project references: 2019A610094 and Beijing University of Technology, Project references: E01210300004. The research study was also supported by the Ningbo Science and Technology Bureau under Grant no: 2021S141.
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2023 The Author(s), under exclusive license to Springer Nature Singapore Pte Ltd.
About this chapter
Cite this chapter
Xia, L., Lun, I. (2023). Analysis of Air Side Cooling and Dehumidification Performance in Evaporator in Direct Expansion (DX) Variable Refrigerant Flow (VRF) Air-Conditioning (A/C) System. In: Enteria, N., Sawachi, T., Saito, K. (eds) Variable Refrigerant Flow Systems. Springer, Singapore. https://doi.org/10.1007/978-981-19-6833-4_4
Download citation
DOI: https://doi.org/10.1007/978-981-19-6833-4_4
Published:
Publisher Name: Springer, Singapore
Print ISBN: 978-981-19-6832-7
Online ISBN: 978-981-19-6833-4
eBook Packages: EngineeringEngineering (R0)