A performance assessment of an office space with displacement, personal, and natural ventilation systems

  • Research Article
  • Indoor/Outdoor Airflow and Air Quality
  • Published:
Building Simulation Aims and scope Submit manuscript

Abstract

This paper presents the results of a field study concerning indoor conditions in an office space in Grieskirchen, Upper Austria. The office is equipped with a displacement ventilation (DV) as well as personal ventilation (PV) systems. The space can also be naturally ventilated through the manual operation of windows (NV). The main objective of the study was to assess the functionality of the mentioned ventilation systems with regard to indoor air quality and thermal comfort. The configuration of the indoor climate control system in this office allows for the performance evaluation of the ventilation systems through different methods. In fact, the monitored data and short-term user surveys provide a basis to document the indoor conditions and their implications for the occupants. Our study also illustrated the utility of calibrated CFD models toward a better understanding of the airflow phenomena and estimation of the airflow velocity as an input data for calculation of predicted mean vote (PMV) values. The results suggest that the combined operation of the above mentioned systems provides in general acceptable indoor environmental conditions. However, optimal operation of the systems installed requires the continuous and comprehensive monitoring of indoor conditions, systems states, and occupants’ feed-back.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  • ANSI/ASHRAE (2010). Standard 55: Thermal Environmental Conditions for Human Occupancy. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers.

    Google Scholar 

  • ASHRAE (2009). ASHRAE Handbook Fundamentals. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers.

    Google Scholar 

  • ASHRAE (2007). Standard 62.1: Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers.

    Google Scholar 

  • Bordass B, Leaman A (2009). An overview of post-occupancy evaluation. SEDA Seminar, The Lighthouse, Glasgow, UK.

    Google Scholar 

  • Cândido C, de Dear RJ, Lamberts R, Bittencourt L (2010). Air movement acceptability limits and thermal comfort in Brazil’s hot humid climate zone. Building and Environment, 45: 222–229.

    Article  Google Scholar 

  • Cermak R, Melikov AK, Forejt L, Kovar O (2006). Performance of personalized ventilation in conjunction with mixing and displacement ventilation. HVAC&R Research, 12: 295–311.

    Article  Google Scholar 

  • Chakroun W, Ghaddar N, Ghali K (2011). Chilled ceiling and displacement ventilation aided with personalized evaporative cooler. Energy and Buildings, 43: 3250–3257.

    Article  Google Scholar 

  • Chen Q, Srebric J (2002). A procedure for verification, validation, and reporting of indoor environment CFD analyses. HVAC&R Research, 8: 201–216.

    Article  Google Scholar 

  • Chen Q, Zhai Z (2004). The use of CFD tools for indoor environmental design. In: Malkawi A, Augenbroe G (eds), Advanced Building Simulation. New York: Spon Press, pp. 119–140.

    Google Scholar 

  • Conceição E, Lúcio MM, Rosa S, Custódio A, Andrade R, Meira M (2010). Evaluation of comfort level in desks equipped with two personalized ventilation systems in slightly warm environments. Building and Environment, 45: 601–609.

    Article  Google Scholar 

  • Dalewski M, Melikov AK, Vesely M (2014). Performance of ductless personalized ventilation in conjunction with displacement ventilation: Physical environment and human response. Building and Environment, 81: 354–364.

    Article  Google Scholar 

  • Dalewski M, Veselý M, Melikov AK (2012). Ductless personalized ventilation with local air cleaning. In: 10th International Conference on Healthy Buildings, Brisbane, Australia.

    Google Scholar 

  • Davis (2015). Professional Quality Weather Stations and Software, Automotive Tracking, and Marine Accessories by Davis. Available at http://www.davisnet.com. Accessed 1 Apr 2015.

    Google Scholar 

  • DesignBuilder (2011). DesignBuilder CFD—Computational Fluid Dynamics. Available at http://www.designbuilder.co.uk/content/view/152/226/. Accessed 1 Apr 2015.

    Google Scholar 

  • DOE (2015). EnergyPlus Energy Simulation Software. US Department of Energy. Available at http://apps1.eere.energy.gov/buildings/ energyplus. Accessed 1 Apr 2015.

    Google Scholar 

  • EDR (2015). Design Brief: Displacement Ventilation 2.0. In: Energy Design Resources. Available at http://energydesignresources.com/ resources/publications/design-briefs/design-brief-displacementventilation. aspx. Accessed 1 Apr 2015.

    Google Scholar 

  • Emmerich SJ, Mcdowell T (2005). Initial Evaluation of Displacement Ventilation and Dedicated Outdoor Air Systems for U.S. Commercial Buildings. US Environmental Protection Agency.

    Google Scholar 

  • Halvonova B, Melikov AK (2010a). Performance of ductless personalized ventilation in conjunction with displacement ventilation: Impact of workstations layout and partitions. HVAC&R Research, 16: 75–94.

    Article  Google Scholar 

  • Halvonova B, Melikov AK (2010b). Performance of “ductless” personalized ventilation in conjunction with displacement ventilation: Impact of intake height. Building and Environment, 45: 996–1005.

    Article  Google Scholar 

  • Halvonova B, Melikov AK (2010c). Performance of “ductless” personalized ventilation in conjunction with displacement ventilation: Impact of disturbances due to walking person(s). Building and Environment, 45: 427–436.

    Article  Google Scholar 

  • Hamilton SD, Roth KW, Brodrick J (2004). Emerging technologies: Displacement ventilation. ASHRAE Journal, 46(9): 56–58.

    Google Scholar 

  • John DA (2011). designing for comfort: Selecting air-distribution outlets. ASHRAE Journal, 53(9): 38–46.

    Google Scholar 

  • Junjing Y, Sekhar C, Cheong D, Raphael B (2014). Performance evaluation of an integrated personalized ventilation—Personalized exhaust system in conjunction with two background ventilation systems. Building and Environment, 78: 103–110.

    Article  Google Scholar 

  • Kaczmarczyk J, Melikov AK, Fanger PO (2004). Human response to personalized ventilation and mixing ventilation. Indoor Air, 14: 17–29.

    Article  Google Scholar 

  • Kaczmarczyk J, Melikov AK, Sliva D (2010). Effect of warm air supplied facially on occupants’ comfort. Building and Environment, 45: 848–855.

    Article  Google Scholar 

  • Kim J, de Dear R, Cândido C, Zhang H, Arens E (2013). Gender differences in office occupant perception of indoor environmental quality (IEQ). Building and Environment, 70: 245–256.

    Article  Google Scholar 

  • Lesbirel M (2012). LEED post-occupancy surveys: Designing a survey for maximum return. Brown University, USA.

    Google Scholar 

  • Li R, Sekhar SC, Melikov AK (2010). Thermal comfort and IAQ assessment of under-floor air distribution system integrated with personalized ventilation in hot and humid climate. Building and Environment, 45: 1906–1913.

    Article  Google Scholar 

  • Lin YJP, Lin CL (2014). A study on flow stratification in a space using displacement ventilation. International Journal of Heat and Mass Transfer, 73: 67–75.

    Article  Google Scholar 

  • Magnier L, Zmeureanu R, Derome D (2012). Experimental assessment of the velocity and temperature distribution in an indoor displacement ventilation jet. Building and Environment, 47: 150–160.

    Article  Google Scholar 

  • Melikov AK (2004). Personalized ventilation. Indoor Air, 14: 157–167.

    Article  Google Scholar 

  • Melikov AK, Cermak R, Majer M (2002). Personalized ventilation: Evaluation of different air terminal devices. Energy and Buildings, 34: 829–836.

    Article  Google Scholar 

  • Melikov AK, Grønbæk H, Nielsen JB (2007). Personal ventilation: From research to practical use. In: Proceedings of Clima 2007, WellBeing Indoors, Helsinki, Finland.

    Google Scholar 

  • Melikov AK, Ivanova T, Stefanova G (2012). Seat headrest-incorporated personalized ventilation: Thermal comfort and inhaled air quality. Building and Environment, 47: 100–108.

    Article  Google Scholar 

  • Melikov AK, Kaczmarczyk J (2012). Air movement and perceived air quality. Building and Environment, 47: 400–409.

    Article  Google Scholar 

  • Niu J, Gao N, Phoebe M, Huigang Z (2007). Experimental study on a chair-based personalized ventilation system. Building and Environment, 42: 913–925.

    Article  Google Scholar 

  • Rees SJ, Haves P (2013). An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling. Building and Environment, 59: 358–368.

    Article  Google Scholar 

  • Rogers G (2015). ALMEMO System Measuring Instruments and Data Logging Systems from IDS Industry. Available at http://inds.co.uk/ almemo/index.htm. Accessed 1 Apr 2015.

    Google Scholar 

  • Russo J (2011). A Detailed and Systematic Investigation of Personal Ventilation Systems. PhD Thesis, Syracuse University, USA.

    Google Scholar 

  • Schiavon S, Melikov AK (2009). Energy-saving strategies with personalized ventilation in cold climates. Energy and Buildings, 41: 543–550.

    Article  Google Scholar 

  • Schiavon S, Melikov AK, Sekhar C (2010). Energy analysis of the personalized ventilation system in hot and humid climates. Energy and Buildings, 42: 699–707.

    Article  Google Scholar 

  • Schiavon S, Rim D, Pasut W, Nazaroff WW (2014). Sensation of draft at ankles for displacement ventilation and underfloor air distribution systems. In: Proceedings of 13th International Conference on Indoor Air Quality and Climate, Hong Kong, China.

    Google Scholar 

  • Sekhar SC, Gong N, Tham KW, Cheong KW, Melikov AK, Wyon DP, Fanger PO (2005). Findings of personalized ventilation studies in a hot and humid climate. HVAC&R Research, 11: 603–620.

    Article  Google Scholar 

  • Thermokon (2015). Thermokon Sensortechnik GmbH. Available at http://www.thermokon.de. Accessed 1 Apr 2015.

    Google Scholar 

  • Titus (2014). Displacement Ventilation. Available at https://www.titushvac. com/docs/2014 catalog/displacement_2013.pdf. Accessed 1 Apr 2015.

    Google Scholar 

  • Veselý M, Zeiler W (2014). Personalized conditioning and its impact on thermal comfort and energy performance—A review. Renewable and Sustainable Energy Reviews, 34: 401–408.

    Article  Google Scholar 

  • Webb M (2013). Building energy and CFD simulation to verify thermal comfort in under floor air distribution (UFAD) design. In: Proceedings of 13th International IBPSA Building Simulation Conference, Chambéry, France, pp. 1886–1893.

    Google Scholar 

  • Wiercinski Z, Skotnicka-Siepsiak A (2008). Application of CFD for temperature and air velocity distribution calculation in a ventilated room. Task Quarterly, 12: 303–312.

    Google Scholar 

  • Xu Y (2007). Modeling and evaluation of personal displacement ventilation system for improving indoor air quality. Open Access Theses, paper 106, Univeristy of Miami, USA.

    Google Scholar 

  • Yang B, Sekhar SC, Melikov AK (2010). Ceiling-mounted personalized ventilation system integrated with a secondary air distribution system—A human response study in hot and humid climate. Indoor Air, 20: 309–319.

    Article  Google Scholar 

  • Zhang H (2003). Human thermal sensation and comfort in transient and non-uniform thermal environments. PhD Thesis, University of California, USA.

    Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to Mahnameh Taheri.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Taheri, M., Schuss, M., Fail, A. et al. A performance assessment of an office space with displacement, personal, and natural ventilation systems. Build. Simul. 9, 89–100 (2016). https://doi.org/10.1007/s12273-015-0252-5

Download citation

  • Received:

  • Revised:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s12273-015-0252-5

Keywords

Navigation